27
byte
type
range
description
Max. load current: 13 HighByte
14 LowByte
UInt16 0 ... 65535
Contains the highest measured current of the channel since
the last reset.
A standardised 16-bit-value with a resolution of 10 mA is
made available.
Example for calculation of the measuring value:
value (150)/100 =^1.50 Amps
Medium value
load current
15 HighByte
16 LowByte
UInt16 0 ... 65535
Contains the mean current value of the channel since the last
reset.
A standardised 16-bit-value with a resolution of 10 mA is
made available.
Example for calculation of the measuring value:
value (150)/100 =^1.50 Amps
Supply
voltage /
actuator voltage
17 HighByte
18 LowByte
UInt16 0 ... 65535
Holds the supply voltage / actuator voltage of the channel.
A standardised 16-bit-value with a resolution of 10 mV is made
available.
Example for calculation of the measuring value:
value (2512)/100 =^25.12 Volt
Reserve
19 HighByte
20 LowByte
UInt16 0 ... 65535
reserve
Diagnostic
information
of the channel
21
byte
0 ... 255
0 = OK
1 = available device type does not match the configured type
2 = no device detected
3 = unused channel
144 = device parameters not plausible
146 = channel off via momentary switch/switch
147 = detected undervoltage
148 = detected excess temperature
149 = reset command required
150 = command was processed correctly
151 = parameterisation required
152 = Internal failure detected
153 = unknown command
154 = set length error
155 = rated current available, check sum error
156 = current rating selector switch was actuated
fig. 26: Dynamic information