21
fig. 20: Dynamic information CPC12
1)
The command »118 = reset device parameters to factory settings including CPC12« within the action commands for the
CPC12 shall reset the following data:
• parameters (current ratings = 10 A, limit value load current = 80 %) of each channel
• PLC lock bit of each channel (default = True, i.e. Channel not to be controlled by the PLC)
•
not the configured device types
•
not the statistical values (min, max, avg) of the channels
•
not the error memory, trip counter and trip reason of the channels
• configuration data
- power saving mode = False = LEDs normal
- behaviour of load outputs in the event of field bus interruption = True = status is maintained
- writing via web server permitted = True
2)
The command »131 = back-to-box« within the action commands for the CPC12 shall reset the following data:
• Parameters (rated current = 10 A, limit value load current = 80 %) of each channel
• PLC lock bit of each channel (default = True, i.e. Channel not controllable by PLC)
• configured device types (default = REX12D-TA1 = 0x9009 = 36873)
• the statistical values (min, max, avg) of the channels
• the error memory, trip counter and trip reason of the channels
• configuration data
- Energy saving mode = False = LEDs normal
- Behaviour of the load outputs on fieldbus interruption = True = Status is maintained
- Writing via web server allowed = True
• IP configuration of the third ETH port X1
- IP address = 192.168.1.1
- Netmask = 255.255.255.0
- gateway = 192.168.1.254
- DHCP = False
• User data
- Name = »admin«
- Password = »admin«
9.1.4 Dynamic information CPC12 controller
byte
type
range
description
cycle time
ELBus
®
1
0 HighByte
1 LowByte
UInt16 0 ... 65535
Holds the internal cycle time of the
ELBus
®
in milliseconds
[ms].
reserve
2 HighByte
3 LowByte
UInt16 0 ... 65535
reserve