20
byte
type
range
description
Action commands 0
byte
0 ... 255
116 = reset trip counter
118 = reset device parameters to factory settings including
CPC12
1)
131 = back to box
2)
132 =
Adjust device configuration to connected device type
(cf. chapter 9.2.3)
192 = reset statistics minimum values
196 = reset statistics maximum values
220 = reset statistics mean values
Other values will not be accepted.
byte
type
range
description
Configuration
data of the CPC
0
byte
0 ... 255
bit 0 = writing via web server permitted. Allows changing of
parameters via the server even when the bus connec-
tion is active.
Bit 1
True: In the event of a fieldbus interruption, the status of the
load outputs is maintained.
False: In the event a fieldbus interruption, all load outputs
will be set to the status OFF.
bit 2 = power saving mode, the LEDs will be dimmed for
power reduction.
bit 3 = reserve
bit 4 = reserve
bit 5 = reserve
bit 6 = reserve
bit 7 = reserve
If not described otherwise, »True« means that the function is
active.
Control
commands
disable
ELBus
®
1 on CPC channel
1 ... 16
1 HighByte
2 LowByte
UInt16 0 ... 65535
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel cannot be
switched on or off via the control unit.
Control
commands
disable
ELBus
®
1 on CPC channel
17 ... 32
3 HighByte
4 LowByte
UInt16 0 ... 65535
Each bit represents a channel.
(bit 0 = channel 17; bit1 = channel 18 ...)
If the bit is set, this means that the channel cannot be
switched on or off via the control unit.
Reserve
5 HighByte
6 LowByte
UInt16 0
reserve
Reserve
7 HighByte
8 LowByte
UInt16 0
reserve
fig. 18: Configuration data CPC12
fig. 19: Action commands CPC12
9.1.2 Configuration data CPC12 controller
The device configuration data for the controller consists of 5 bytes.
Access: slot = 1, channel = 0 and parameter index = 3
All configuration data with possible conditions are described in the following table.
9.1.3 Action commands CPC12 Controller
The action commands of the controller consist of 1 byte. All action commands being sent to the CPC12 carry out the action for
all channels.
Access: slot = 1, channel = 0 and parameter index = 5
Action commands with possible conditions are described in the following table.