18
9 Non-cyclical data
Non-cyclical PROFINET services allow exchange of more data with the CPC12 controller and the circuit protectors. Access also
allows direct addressing of a circuit protector. PROFINET - index and slot number are used for this. For reading and editing CPC12
data, slot 1 is used. Slot 2 is used for reading and editing the of circuit protectors. The access to the circuit protectors is divided
into channels. Two channels are provided per circuit protector.
The PROFINET index is set up as follows:
The non-cyclical access to the data of CPC12 is divided as follows:
range
index digit
description
Channel no. on
ELBus ®
Decimal numbers 10
3
and 10
2
Number of channel to be queried.
Valid value range: 01… 32.
Parameter index
Decimal numbers 10
1
and 10
0
The parameter index defines the data range and
the data type of the data to be read/written.
Valid value range: 01… 10.
slot
parameters
Index
channel
number
number of
data bytes
reading (R)
writing (W)
description
1
02
0
19
R
Device information of CPC12 controller
(see chapter 9.1.1).
1
03
0
5
R/W
configuration data of CPC12 controller
(see chapter 9.1.2).
1
05
0
1
W
action commands for all channels and the CPC12 controller
(see chapter 9.1.3).
1
06
0
4
R
dynamic information of CPC12 controller
(see chapter 9.1.4).
02 01
parameter index
channel no. (1-32)
fig. 14: set-up of PROFINET index
fig. 15: Division of parameter index CPC12
Содержание ControlPlex CPC12 T Series
Страница 1: ...User Manual ControlPlex Controller CPC12PN...
Страница 29: ...29...