e-Room® Panasonic Stand-Alone

Stand-alone controller for rooms with climate VRF Panasonic system
PAW-RE2C3-WH – White frame
PAW-RE2C3-GR – Gray frame

Instruction Sheet

Introduction

Room controller e-Room® Panasonic Stand-Alone is a device 
designed to perform a global room automation for hotels, 
offi

  ces or homes with climate systems based on VRF Panasonic 

indoor units. The device has a communication protocol which 
allows managing a climate indoor unit without needing other 
remote controls, interacting with the unit when occupied or 
unoccupied room is detected.
The device has digital/analogue inputs which are used to 
detect the occupancy room state through a keycard contact 
or motion sensor and door contact, in addition of a window 
contact which is used to stops climate when the window is 
open. It is possible to control a second zone climate on separate 
rooms like bedroom and bathroom throughout an analogue 
input connecting an external temperature sensor. The device 
includes various relay outputs to control diff erent functions like 
lighting state, motorized curtains or blinds and a second zone 
climate.

There are four possible operating modes on the device; each 
one has a diff erent operating and input/output confi guration, 
which must be selected depending on the installation 
confi guration that better suits to the operating requests. 

Indoor Unit model 2 Ways / 3 Ways

The device should be confi gured to control the Indoor Unit 
installed. The 2 ways (2P) unit confi guration allows user 
selecting between COOL and HEAT throughout HEAT and COOL 
pushbutton while the 3 ways (3P) machine confi guration allows 
user selecting between HEAT, COOL and AUTO. On AUTO mode, 
the machine automatically decides between HEAT/COOL 
depending on ambient temperature and set-point temperature 
confi gured.

Mode OFF/ECO

OFF/ECO mode is used to stop the device or change climate 
into ECO mode when room turns to unoccupied. If ECO mode 
is confi gured, set-point temperature automatically changes 
into economy value preset on HEAT or COOL parameter 
confi guration. 

User and real setpoint temperatures

The device has diff erent maximum and minimum set-point 
temperatures to limit values to defi ne by user. Maximum set-

point temperature is used to limit maximum value on heat 
mode and minimum set-point temperature is used to limit 
minimum value on cool mode.

Maximum/minimum user set-point temperatures are 
maximum and minimum values that user can set throughout 
the pushbuttons. 

Maximum/minimum real set-point temperatures are maximum 
and minimum values that perform to the machine. Real values 
override values which user sets.

AutoOn Mode

The device has an automatic switch on mode to prevent that 
a zone temperature exceeds a preset maximum temperature 
value in summer or a minimum temperature value in winter. For 
that reason the device has a temperature value for AutoOn in 
HEAT mode and another temperature value for AutoOn in COOL 
mode, as well as two parameters to enable each operating 
mode in a separated way.

The AutoOn mode is automatically activated when the ambient 
temperature is 1 degree diff erent from AutoOn set-point value 
and automatically deactivates when temperature is 2 degree 
diff erent from the set-point value.

AutoOn mode is only activated when room is unoccupied 
and if the device is confi gured to changes into OFF state with 
unoccupied room. 

Indicated temperature values are in Celsius degrees.

Climate restart when power-up

The device can be confi gured in order to automatically restart 
climate after voltage drops. On the other hand, it is possible to 
confi gure the climate mode with which is desired the device 
restarts. 

Blinds control

The devices includes a function in order to automatically 
raise blinds up when room changes into occupied state or 
automatically lower blinds down when room changes into 
unoccupied state.
This function is especially useful if it is desired that blinds raise 
up when user enters in the room, or that blinds lower down to 
preserve room temperature when the user leaves the room. 

Product description

e-Room® Panasonic Stand-Alone is a device desig-

ned to perform a global room automation, providing 
a high comfortable level, an energy cost reduction, 
and a better integration of the rooms in the building. 

The device enables or stops an indoor unit climate, 

lighting and curtains control and manages the state of a 
secondary zone climate when room changes into occupied 
or unoccupied state, reducing energetic consumption and 
effi

  ciency integrating climate into global room control.

The device is a compact unit that includes a large 

backlight display screen, a built in temperature sen-
sor, pushbuttons on the front panel, and inputs and 
outputs for a global control of the main room services.

© 2014 e-Controls®

INS1114507000-0 

 

 

 

             1

Содержание e-Room Panasonic Stand-Alone

Страница 1: ...point temperature is used to limit maximum value on heat mode and minimum set point temperature is used to limit minimum value on cool mode Maximum minimum user set point temperatures are maximum and minimum values that user can set throughout the pushbuttons Maximum minimum real set point temperatures are maximum and minimum values that perform to the machine Real values override values which use...

Страница 2: ...is enabled and can operate When window is opened climate system stops working leaving the room temporarily without climate The device screen displays an open window icon and disappear the AUTO or fan coil speeds icon just in case the device is in Device inputs operation MANUAL mode Climate zone number 2 controlled by valve actuator also deactivates while window is open When window is closed again ...

Страница 3: ...int depending on mode climate at that moment If room has been changed into unoccupied state and after that any motion is detected system enables again the device and room will be in Occupied state NOTE This operating mode can interact with Courtesy lighting output OUT1 and Lighting OUT2 This operating is described on Device outputs operating description section Device inputs operation continuation...

Страница 4: ...coil speed following the sequence I II III AUTO After speed III AUTO mode is selected again Set point temperature Set point temperature value increments or decrements until maximum and minimum limits configured on the device 5 seconds after the last press the device returns to resting state displaying ambient temperature or set point temperature depending on how it has been configured After 10 sec...

Страница 5: ...speed indicator It indicates the fan coil speed between the possible selection LOW MED and HIGH and operating mode selected AUTO Manual Display description When some operating failure exists on the installation or the device display shows the alarm detected throughout a number and the alarm sign icon and the blinking red LED Device can show three possible types of alarms Operating alarm The corres...

Страница 6: ...T4 Unit Indoor L1 Courtesy Lighting L2 Room Lighting C1 Contactor C1 Inputs Dry Contact Outputs Max 5A 250Vac contact Indoor Unit Neutral Phase Lighting Window 16 15 14 13 12 11 10 9 1 2 3 4 5 6 7 8 R1 R2 OUT2 e Room Panasonic Model Stand Alone Supply R1 R2 100mA IP20 Made in Spain www e controls es R 16 15 14 13 12 11 10 9 7 8 6 5 4 3 2 1 R1 R2 IN2 IN1 IN4 IN3 OUT1 OUT3 OUT4 Unit Indoor Up Down C...

Страница 7: ... of electrical systems for household HBES and automation and control systems for buildings BACS EN 50491 3 2009 CE Conformity Low Voltage Directive LVD 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Standards Electrical safety EN 50491 3 2009 EN 50491 4 1 2012 Electromagnetic Compatibility EN 50491 5 1 2010 EN 50491 5 2 2010 Technical features e Room Panasonic Stand Alone white fra...

Отзывы: