INSTALLATION INSTRUCTIONS
C-AR-B-DD Series
http://lighting.cree.com/warranty | 1-800-236-6800
CAUTIONS
lead to the negative dimming lead.
If dimming is not be used, make sure the violet and gray
fixture leads are capped off.
NOTE:
Dimming should only be used if the fixture is set to
60 W in Step 9 below.
6.
Slide fixture onto two lag bolts from Step 3 and install third
lag bolt in top slot of fixture. Secure all lag bolts.
7.
Secure cover plate with (2) Allen bolts, lock washers, and
flat washers. Position lock washer under bolt head and flat
washer between lock washer and cover plate. Discard arm
bracket.
8.
Install the photo-control by aligning the arrow on the top
of the photo-control with the arrow on the photo-control
socket and inserting pins into the socket. Twist photo-
control clockwise. (Photocontrol must be rotated at least
1/8 turn to properly lock in place). See
Figure 3.
NOTE:
Improper installation of the photo-control may result
in damage to the photo-control.
9. Remove threaded plug from top surface of fixture and
position toggle switch for desired wattage (See
Figure 4
on next page
):
•
I = 29W
• II = 40W
• III = 60W
10.
Replace plug removed in Step 9 above.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. DANGER
- Risk of shock- Disconnect power before
installation.
DANGER
– Risque de choc – Couper l’alimentation
avant l’installation.
2.
SUITABLE FOR WET LOCATIONS.
CONVIENT AUX EMPLACEMENTS MOUILLES.
3. SUITABLE FOR OPERATION IN AMBIENT NOT
EXCEEDING 50°C.
PEUT ETRE UTILISE A UNE TEMPERATURE
AMBIANTE N’EXCEDANT PAS 50°C.
4.
INSTALL PHOTOCONTROL OR SHORTING PLUG
.
INSTALLER UNE CELLULE PHOTOELECTRIQUE OU
UNE PRISE COURT-CIRCUITANTE.
5.
CLASS 1 WIRING ONLY. When dimming cord provided
SAVE THESE INSTRUCTIONS FOR
FUTURE REFERENCE
FIGURE 1
C-AR-B-DD SERIES-
DIRECT MOUNTED
DIRECT MOUNTING
1.
Install fixture cover plate to conduit using either knockout.
2. Use fixture to mark the location for the lag bolts on
mounting surface.
3. Install two lower lag bolts into mounting surface, allowing
the head of each bolt to remain 1/4” (6.4 mm) from
mounting surface.
4.
Wire black fixture lead to the incoming voltage supply
or Hot 1 lead and the white fixture lead to the incoming
neutral (Common) or Hot 2 lead. Attach bare copper or
green ground fixture lead to the incoming ground lead.
5.
If 0/1-10V dimming is used, connect the violet fixture lead
to the supply positive dimming lead and the gray fixture
FIGURE 2- Items Included with Fixture