A48100 Unit User Manual
20
3.2.4 Battery parameter settings on the inverter
Max Charging(Bulk) Voltage: 53.5V
Absorption Voltage: 53V
Float Voltage: 52.5V
Shut Down(cut off) Voltage: 47V
Shut Down(cut off) SOC: 20%
Restart Voltage: 49V
Max Charge Current: 50A*battery QTY
Max Discharge Current: 50A*battery QTY
3.2.5 Register on the website after installation
After the battery system installation is completed and the running is normal, you need to log
in to the DYNESS official website to register the product installation and use information to
make the product warranty effective. Please follow the instructions on the website to register.
Service