A.3 Power On/Off Sequences
A.3.1 Power On in Standby
.
Three
Seconds
Two
Seconds
.
.
.
.
Unit Power On
Firmware Version Info:
Major Version = 03
Minor Version = 00
Revision Number = 22
Host Port Info:
Unit ID = 01
Baud Rate = 115.2kbps (115200bps)
Meters Run Screen:
Unit is in standby mode (output disabled).
Power Failure:
Output is disabled, unit is powering off.
Unit Power Off
This is the main menu used
during operation. Various
run screens can be selected,
here the meters are shown.
Power
Lost
Power
OK
Power On Start = Standby
In this configuration the power supply always powers on in standby mode. If a
cycle was running when the unit was powered off the unit will power up in standby
mode with the cycle paused so that it can be manually resumed.
See the unit start system menu for details on how to change the power on start
configuration.