                                                                      important notes 
 

 

 
 

 

  

 

 
 
 
 

4  x  Dry  Contact  Inputs

 

–  Presented  on  a  2.5mm  pitch 

165mm long fly leads. 

 

Powered from the DALI Network 

– 

No need for an external 

power supply. 

 

DALI  network 

–  Different  DALI  network  devices  can  be 

connected  in  any  order  along  the  network.  The  DPMI940-
DALI  does  not  need  to  be  directly  connected  to  the  lighting 
groups that is controlling 

 

Simple Installation - 

Compact enclosure allows the device to 

be  conveniently  placed  near  the  device  to  be  controlled.  All 
connections are accessible without disassembly

 

Read  Instructions

 

–  We  recommend  that  you  read  this 

Instruction Manual prior to commencement of installation. 

 
Special  Programming

 

–  This  device  will  only  operate  in  basic 

modes  unless  programmed  via  a  computer.    Device  is  to  be 
commissioned using Envision software. 

 
DALI bus ready 

– This device can only be used in junction with a 

Philips  Dynalite  multi  master  controller  such  as  the  DDBC120-
DALI. DALI is a non polarised communication protocol.  

 
Installation  Location

 

–  Install  in  a  dry  location,  close  to  the 

equipment to be interfaced with.  

 
Dry  contact  wires:

  Maximum  recommended  length  of  dry 

connector  wires  is  1 meter. Wires should  be  kept  away  from  any 
mains  cables.  Inputs  must  not  be  connected  to  any  voltage 
source, only voltage free dry contacts should be used  
 
 

Flying Lead inputs 

 

wire

 

Function

 

Colour

 

COM

 

Purple 

DC1

 

GREY 

DC2

 

GREY 

DC3

 

GREY 

DC4

 

GREY 

DA

 

ORANGE 

DA

 

ORANGE 

 

……… 

DPMI940-DALI 

 

DALI Auxiliary Input Interface   
Installation Manual 

features  

 

Electrical diagram

 

Connecting volt free inputs 
diagram

WARNING: 

Do  not  connect  DALI  or  Dry  contact 

wires  to  mains.  Dry  contact  &  DALI  wires  are  NOT 
SELV  and  should  never  be  considered  touch  safe. 
Functional  level  of  isolation  or  better  is  required 
between DALI / dry contact wires and mains cabling. 

 