Configuration
27
© 2012 DynaGen Technologies Inc.
TOUGH Series User Manual
AMF / ATS Inputs
The following inputs are only available in the TG350AMF version of the controller. See
for
more information on how these inputs function.
FUNCTION
ACTIVE MODE
DESCRIPTION
Generator Position
Global
Indicates the current position of the user operated
transfer switch. See
for more
information.
Mains Position
Transfer to Generator
Running
Causes the ATS to change to the generator
position when in Manual ATS mode. See
for more information.
Transfer to Mains
Auto / Running
Causes the ATS to change to the mains position
when in Manual ATS mode. See
for more information.
Test Mains Failure
Auto
Simulates loss of mains to test AMF features.
4.2.1
Voltage Select
The controller can be configured to display different AC voltages depending on the status of the 'Volt
Select' switched inputs. In order for this feature to function properly, the 'Genset Voltage Source' setting
must be set to 'Auto Selection' and the 'Voltage Select Inputs' settings found in
must
be configured. The following table demonstrates the relationship between the switched inputs and the
monitored voltage source.
NOTE
: Changing the voltage select inputs while the generator is running will have no effect.
They must be changed prior to starting up.
VOLT SELECT 1
VOLT SELECT 2
VOLTAGE SOURCE
Inactive
Inactive
3-Wire Single Phase
Inactive
Active
4-Wire 3-Phase
Active
Inactive
4-Wire 3-Phase
Active
Active
4-Wire Delta
This application is generally used with rental generators that have the ability to use a CAM switch to
change the voltage configuration.
39
39
39
39
38