Settings
35
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.4
Sensors
The controller has four sensor inputs which can be connected to a variety of different sensors/switches depending on the input.
See the
section for more information regarding the sensor types supported.
To configure the behavior of these sensor inputs the user assigns the sensor input to one of the following 7 sensor functions:
·
Engine Temperature,
·
Oil Pressure,
·
Fuel Level
·
Auxiliary Sensor 1
·
Auxiliary Sensor 2
·
Auxiliary Sensor 3
·
Auxiliary Sensor 4
Note that there are more sensor functions than sensor inputs as the Auxiliary Sensors can be assigned the same sensor input
as the other sensor functions.
·
The Engine Temperature, Oil Pressure, and Fuel Level functions are mostly fixed in functionality but the
sensors
can be configured to perform specific shutdowns or special functions (Example: Starting engine on low temperature).
·
The Engine Temperature, Oil Pressure, and Fuel Level functions can be set to work with a switch or a sender/sensor but the
Auxiliary sensors can only work with a sender.
Note: The engine speed and battery level are built in and do not need to be assigned to a pin.
4.4.1
Engine Temperature
Use the following settings' configurations to allow the controller to read and interpret data from the engine temperature sensor
or switch.
(Sensors > Engine Temp. menu)
Name
Range
Default
Settings
Description
Signal Source
Port A
Port B
Port C
Port D
J1939 Bus*
Port A
The sensor input pin where the engine temperature switch or sender is
attached.
*Engine temperature is obtained from the engine controller (ECM)
using the CANbus communication port and J1939 protocol.
Sensor Type
DAT DAH*
VDO 250F*
(custom sender)**
Close = Warning
+
Open = Warning
+
Close = Failure
+
Open = Failure
+
DAT DAH Select the sender that is connected to the Signal Source above. If
using a switch select the action that should occur when the switch is
active.
*These are preprogrammed into the controller and cannot be changed.
- DAT DAH supports all Datcon type DAH (high range) temperature
sensors such as 02022-00.
- VDO 250F supports the VDO 323-420 or equivalent temperature
sensor.
DAT DAH and VDO 250F can only be used if the Signal Source is set
to Port A or D. To use on other ports store as a custom sender table
using the RapidCore Configuration software.
**A custom table can be created using the RapidCore Configuration
Software. The text (custom sender) will be replaced with the custom
text you choose when creating the sender.
+
The switch must close to ground.
Trim Offset
-50.0 ~ 50.0°F (-
10 ~ 10
0
C)
0.0 F
Calibrate a sensor by using the offset to correct errors. Only applies if
Sensor Type has been set to a sender.
Setpoints > Bypass
Time
0 ~ 90 seconds
30 s
Amount of time to bypass warnings and failures after engine has
started.
Setpoints > Low
Warn (Low
Warning)
Disabled, 32 ~
200°F (0 ~ 93.3
0
C)
Disabled
Reading at which a "Low Engine Temp" warning occurs. Displays 'Low
Engine Temp' on the screen. Only applies if Sensor Type has been set
to a sender. Monitored globally including OFF and AUTO.
Setpoints > High
Warn (High
Warning)
Disabled, 50 ~
300°F (10 ~
148.9
0
C)
200 F
Reading at which a "High Engine Temp" warning occurs. Only applies if
Sensor Type has been set to a sender. Only monitored in the RUN
mode.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...