Settings
31
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.2.1
Configurable Inputs
These inputs are used to create custom warnings and failures. Using the RapidCore Configuration Software you can change
the text displayed when the warning or failure occurs. If you select one of these inputs without changing the text it will default to
'Config Warn X' and 'Config Fail X.'
There are also timers associated with the configurable inputs which can be found in the menu under
Timers > Trigger Delays >
Config Inputs and Config Fail 3
. These timers change the amount of time the input has to be active before the controller
registers the warning or failure.
NOTE
: If the switched input becomes inactive before the trigger delay time expires, the warning or failure will not
occur.
Example:
The user wants a pump to turn on 30 seconds after a high water level switch is tripped and remain on until the level
switch turns off.
The level switch is connected to Switched Input C and closes to ground when the water level is too high. The words 'Water
Pumping' are also required to be displayed on the controllers LCD screen. The pump is connected to a slave relay which is
controlled by Switched Output D on the controller.
Relevant Settings
Setting
Value
Switched Input C -> Function
Configurable Warning 1
Switched Input C -> Active Mode
Global
Switched Input C -> Trigger
Close GND
Configurable Warning 1 Custom Text
Water Pumping
Switched Output D -> Warnings
Configurable Warning 1
4.3
Switched Outputs
The controller has switched outputs that are turned on under certain conditions to perform a function. The outputs turn on to
+Battery voltage to drive the load when active. The following items are the available functions for switched outputs.
WARNING
: Switched outputs have a floating voltage of approximately 8V when off. If using the outputs for digital
logic, it will be necessary to put a pull-down resistor (1 kOhm) from the output to ground to ensure a low logic level
when output is off.
Default settings:
Switched
Output
Default Setting
Switched
Output A
Fuel Output
Switched
Output B
Disable
Switched
Output C
Crank Output
Switched
Output D
Disable
Switched
Output E
Disable
Switched
Output F
Disable
Event Functions
Name
Active Mode
Description
Fuel
Cranking, Running
Active during cranking and running to supply fuel to engine.
Crank
Cranking
Active during cranking to start the engine.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...