Settings
27
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
4.2
Switched Inputs
The controller has switched inputs which cause the controller to perform a function when activated.
Switched I/O > Switched IN X:
Name
Range
Description
Function
[Menu] See below.
The function that the switched input performs when active.
Active Mode
[Menu] See below.
Determines the operating conditions under which the switched input can be
active. Multiple selections are allowed.
Trigger
[Menu] See below.
The state of the input determining if it is active or inactive.
Switched I/O > Switched IN X > Function:
Name
Active Mode
Description
Disabled
N/A
Input is disabled and has no function.
Start / Stop
Auto, Running
Starts the engine when active, stops the engine when deactivated. It is
recommended to set the Trigger mode to Close +BAT for better noise
tolerance.
Emergency Stop
Global
When active, shuts down the engine, displays Emergency Stop, and
prevents leaving the OFF mode.
CAUTION !!! This should only be used for emergency stop indication on the
controller. The installer must provide an independent means to shut down
the engine from the emergency stop button such as cutting off fuel. See the
typical wiring diagrams for an example on how to wire up the emergency
stop.
Idle Mode
Running
See the
section under Engine Logic for more information.
Voltage Select 1
Auto
Used for changing the system AC voltage configuration. See
Voltage Select 2
Auto
Charger Fault (Battery
Charger Fault)
Global
Controller displays 'Charger Fault' warning when active.
Mom. Start (Momentary
Start)
Auto
Starts or stops the engine when momentarily active (Approximately 2
seconds).
These inputs
allow the user to wire separate inputs for start and stop or to
use a push button instead of a toggle switch.
Mom. Stop (Momentary
Stop)
Running
Configurable Warning 1
Configurable
Controller displays a warning or failure with configurable text* when active. In
the case of the configurable failures a shutdown is also performed.
The RapidCore Configuration Software must be used to change the text.
Configurable Warning 2
Configurable
Configurable Failure 1
Configurable
Configurable Failure 2
Configurable
Configurable Failure 3
Configurable
Air Press. Fail (Air
Pressure Failure)
Cranking
Controller displays 'Low Air Pressure' and shuts down engine when active.
Hyd Pres. Fail (Low
Hydraulic Pressure
Failure)
Cranking
Controller displays 'Hydraulic Pressure Failure' and shuts down engine when
active.
Oil Pres Warn (Low Oil
Pressure Warning)
Running
Controller displays 'Oil Pressure Warning' when active.
Cool. Lvl Fail (Low
Coolant Level Failure)
Global
Controller displays 'Low Coolant Lvl' and shuts down engine when active.
High Fuel Warning
Global
Controller displays 'High Fuel Level' warning when active.
Lamp Test
Global
Controller performs lamp test when active. If the controller is in the FAILURE
mode the LED will remain red. The only indication that the lamp test is
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...