background image

 
 
 

 

 
 
 
 

 

 

 

 

 

 
 

 

 
 
 
 
 
 
 
 
 
 
 

Installation and User Manual for the GSC200 Controller 

 

 
Full Version

  

 

File:  GSC200_R1_1doc   
8/12/2008 

 

 

 

GSC200

 

Auto Start Engine & Transfer Switch 

Controller

 

Содержание GSC200

Страница 1: ...Installation and User Manual for the GSC200 Controller Full Version File GSC200_R1_1doc 8 12 2008 GSC200 Auto Start Engine Transfer Switch Controller ...

Страница 2: ...led used or serviced other than in conformity with the Seller s application specifications manuals bulletins or instructions or if none shall have been subjected to improper installation misuse or neglect The warranties shall not apply to any materials or parts thereof furnished by the Buyer or acquired from others at the Buyer s request and or to the Buyer s specifications or designs The foregoin...

Страница 3: ...ications High intensity LED s with regulated brightness LCD Display LCD display for hour meter Adjustments Warm up 0 200 seconds After Failure Bypass Feature Cool Down 0 300 seconds in 5 second increments Crank Disconnect 12 to 140Hz Overspeed 40 200Hz Underspeed 40 200Hz Crank Rest 4 32 seconds GREEN Engine Run LED will flash during Crank Rest Delay on Start 0 59 seconds GREEN Engine Run LED will...

Страница 4: ...eed Sensing Generator Output Speed Sensing Maximum Input Voltage 300VAC RMS Minimum Input Voltage 0 7VAC RMS Generator Output Sensing 60Hz Rejection Filter Included Loss of Speed Signal Included Failure Inputs Oil Pressure Coolant Temperature 2 Auxiliary Inputs Programmable for switch configuration NO or NC ...

Страница 5: ... outputs switched to battery sourcing 2 Auxilliary Outputs User configurable to one of 6 different options through software Connections Removable terminal blocks for input and output connections Programming Windows based software interface utilizing the parallel port of your PC Needs no power to program using the PC Interface uses power from parallel port of PC Specifications May Change Without No...

Страница 6: ...s of speed LED Underspeed If Enabled Underspeed failure is indicated by a flashing RED Loss of speed LED The Underspeed failure will only occur when the Underspeed condition remains for more than 3 seconds LOW BATTERY VOLTAGE INDICATION When the battery voltage drops below the user defined set point which can be programmed between 7 and 35VDC the controller will illuminate the RED Low battery LED ...

Страница 7: ... The last digit on the hour meter will represent the time in 1 10 s of an hour Please note that the accumulated time displayed on the hour meter can not be reset EXERCISER FUNCTION The exerciser function is programmable only through the front panel buttons When the controller is first powered up in Auto mode the Engine Run LED will flash to indicate that the Exerciser Function has not been program...

Страница 8: ......

Страница 9: ...y Available OverCrank Failure OverSpeed Loss Speed Low Batt Engine Run Aux Auto Manual Off LCD Display AUTO LED GREEN The Auto LED will illuminate when the controller is placed into Auto HIGH TEMP LED RED The High Temp LED will illuminate when the High Temperature switch activates LOW OIL LED RED The Low Oil LED will illuminate when the Low Oil switch activates OVERCRANK LED RED The Overcrank LED ...

Страница 10: ...different functions by the user Both Auxiliary outputs can also be disabled in the software When the chosen function of Auxiliary Output 1 goes active the Auxiliary LED will flash as the indication When the chosen function of Auxiliary Output 2 goes active the Auxiliary LED will be steady on to indicate the failure NORMAL AVAILABLE LED GREEN The Normal Available LED will illuminate when the Voltag...

Страница 11: ...amming of the Exerciser the controller will immediately perform an Exerciser cycle The cycle begins with the GREEN Engine Run LED beginning to blink for 60 seconds this is the alert that an Exerciser cycle is about to begin Once the alert time expires the generator will start and if LOAD is selected in the Configurator software the transfer switch will transfer to the generator source If NO LOAD i...

Отзывы: