Specifications - Installation and Operating Instructions

Vane Operated Flow Switch

3-11/32
[84.93]

2-1/2

[63.5]

8

[203.2]

6-3/4

[171.45]

4-11/16

[119.06]

1 [25.4]

U.L. AND C.S.A. TYPE
INCLUDES 16 GA.
LEADS, 6 [152.4] LONG.
CENELEC VERSION
INCLUDES TERMINAL 
BLOCK.
EXPLOSION-PROOF
HOUSING WITH 3/4 
[19.05] CONDUIT 
CONNECTION
SWITCH BODY OF SAE 
72 BRASS OR 316SS 
STAINLESS STEEL
1-1/2 NPT

MAGNET KEEPER 430
STAINLESS STEEL
VANE AND VANE BLOCK
316 STAINLESS STEEL

FIVE LAYER VANE 
DESIGNED FOR 1-1/2 
[38.1] TO 8 [203.2] 
PIPES. USABLE IN 
LARGER SIZES.

SPECIFICATIONS

Service:

Gases or liquids compatible with wetted materials.

Wetted Materials:

Vane:

316 SS

Body:

Brass or 316 SS standard.

Magnet Keeper:

430 SS standard, 316 SS optional.

Options:

Other materials also available, consult factory 

(e.g. PVC, Hastelloy, Nickel, Monel, Titanium).

Temperature Limit: 

-4 to 275°F (-20 to 135°C) standard, MT

high temperature option 400°F (205°C) [MT option not UL, CSA,
ATEX, or SAA].

Pressure Limit:

Brass body 1000 psig (69 bar), 316 SS body

2000 psig (138 bar), optional 5000 psig (345 bar) available with
316 SS body and SPDT switch only.

Enclosure Rating:

Weatherproof and Explosion-proof. Listed

with UL and CSA for Class I, Groups C and D; Class II, Groups E,
F, and G. ATEX      0344     II 2 G EEx d IIB T6 -20°C

)

Tamb

)

75°C

EC-Type Certificate No.: KEMA 03ATEX 2383
SAA: Exd II C T6 (T amb=60°C).
Zone I. Also FM approved.

Switch Type:

SPDT snap switch standard, DPDT snap switch

optional.

Electrical Rating:

UL, FM, ATEX and SAA models 10A @

125/250 VAC (V~). CSA models: 5A @ 125/250 VAC (V~); 5A res.,
3A ind. @ 30 VDC (V   ). MV option: 1A @125 VAC (V~); 1A res.,
.5A ind. @ 30 VDC (V   ). MT option: 5A @ 125/250 VAC (V~). [MT
and MV option not UL, CSA, FM, ATEX or SAA].

Electrical Connections:

UL and CSA models: 16 AWG, 6˝ (152

mm) long. ATEX and SAA unit: Terminal block.

Conduit Connection:

3/4˝ female NPT.

Process Connection:

1-1/2˝ male NPT.

Mounting Orientation:

Within 5° of vertical for proper operation.

Units for horizontal installation (vertical pipe with up flow) available.

Set Point Adjustment:

For universal vane: five vane

combinations.

Weight:

4 lb 8 oz (1.9 kg).

Series

V4

Rugged and reliable the Flotect

®

V4 flow switch

operates

automatically to protect equipment and pipeline systems against
damage from reduction or loss of flow. The V4 is time tested being
installed in thousands of pipelines and processing plants around
the world. A unique magnetically actuated switching design gives
superior performance. There are no bellows, springs, or seals to
fail. Instead, a free-swinging vane attracts a magnet within the solid
metal switch body, actuating a snap switch by means of a simple
lever arm.

FEATURES

• Leak proof body machined from bar stock
• Choice of custom vane calibrated for your application, Model V4,  

or field adjustable multilayer vane, Model V4-2-U (see set point 
chart on page 4)

• Weatherproof, designed to meet NEMA 4
• Explosion-proof (listing included in specifications)
• Installs directly and easily into pipeline with a thredolet, tee, or     

flange (see application drawings on page 4)

• Can be used in pipes 1-1/2˝ and up
• Electrical assembly can be easily replaced without removing the 

unit from installation so that the process does not have to be shut  

down

• High pressure rating of 1000 psig (69 bar) with the brass body 

and 2000 psig (138 bar) with the 316 SS body

APPLICATIONS

• Protects pumps, motors and other equipment 

against low or no flow

• Controls sequential operation of pumps
• Automatically starts auxiliary pumps and engines
• Stops liquid cooled engines, machines and processing when 

coolant flow is interrupted

• Shuts down burner when air flow through heating coil fails
• Controls dampers according to flow

Notes:

•  Check all ratings given in the instructions and on the product to

make sure that the product is suitable for your application. Do 
not exceed electrical ratings, pressure ratings, or temperature 
ratings of the product.

•  Disconnect power supply before beginning installation to prevent

possible equipment damage or electrical shock.

MAINTENANCE

Inspect and clean wetted parts at regular intervals. The cover
should be in place at all times to protect the internal components
from dirt, dust, and weather, and to maintain hazardous location
ratings. Disconnect device from the supply circuit before opening
to prevent ignition of hazardous atmosphere.

Northeast Controls Incorporated

Tel: 845-986-8546 | Fax: 845-810-7625

[email protected]

Northeast Controls Incorporated

Tel: 845-986-8546 | Fax: 845-810-7625

www.dwyerstore.com

Содержание W.E. Anderson Flotect V4 Series

Страница 1: ...tomatically to protect equipment and pipeline systems against damage from reduction or loss of flow The V4 is time tested being installed in thousands of pipelines and processing plants around the world A unique magnetically actuated switching design gives superior performance There are no bellows springs or seals to fail Instead a free swinging vane attracts a magnet within the solid metal switch...

Страница 2: ...ion Terminal Block Wire Connections Time Delay Relay On flow decrease Time Delay Relay On flow increase Vertical Up Flow Applications Flange Process Connection 2 2 1 2 3 4 Carbon Steel 316 SS Monel Hastelloy B Hastelloy C 150 300 600 900 Bushing Process Connection 2 2 1 2 4 Hex Flush Brass Carbon Steel 316 SS 304 SS Tee Process Connection 1 1 2 Tee with Bushing Process Connection Both same materia...

Страница 3: ...rtified seal device such as a conduit seal with setting compound suitable for conditions of use and correctly installed shall be provided immediately to the entrance of the electrical housing The certified conduit seal with setting compound and cable shall be rated for a minimum temperature of 80 C Note The switch is deactivated and contacts are in normal condition when there is no flow in the lin...

Страница 4: ...PE 65 32 30 20 23 13 10 6 3 PIPE 210 105 100 50 120 70 60 30 60 48 30 20 4 PIPE 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 6 PIPE 950 475 450 220 550 375 260 180 375 265 180 130 260 200 120 90 130 100 60 50 8 PIPE 1550 850 730 400 1100 700 520 330 725 500 340 240 500 400 240 190 310 250 150 120 10 PIPE 2400 1300 1100 600 1850 1200 870 570 1200 850 570 400 875 700 410 330 650 525 310 25...

Страница 5: ...en von Rohrleitungen und Prozessfirmen eingesetzt Der Wächter basiert auf einem magnetischen Prinzip Es gibt keine Kol ben Federn oder Dichtungen die ausgetauscht werden müssten Das frei schwingende Paddel aktiviert einen Magneten innerhalb des soliden metallischen Körpers der wiederum einen Mikroschal ter auslöst HAUPTMERKMALE Leckagedichter Körper Eine Auswahl an kundenspezifischen Paddeln Modell ...

Страница 6: ...ontakte NACE Heat Treated Koerper Neoprene Schutz Kein elektrisches Gehaeuse geschweisste Verbindungen Klemmleiste Zeitverzoegerungsrelais steigend Zeitverzoegerungsrelais fallend Vertikale Montage Flanschanschluss 2 2 1 2 3 4 Stahl 316 Edelstahl Monel Hastelloy B Hastelloy C 150 300 600 900 Muffenanschluss 2 2 1 2 4 Hex Flush Messing Stahl 316 Edelstahl 304 Edelstahl T Stueck Anschluss 1 1 2 T St...

Страница 7: ...elverschraubungen eingesetzt wer den die bis mindestens 80 C zugelassen sind Gehäuseverschraubung Bei einem EEx d zertifiziertes Gerät muss unverzüglicher Zugang zu dem Inneren des Ge häuses gewährleistet sein Das Kabelmaterial und die Durchgangsdichtung sollten mindestens bis 80 C geeignet sein Bemerkung Der Wächter ist deaktiviert und die Kontakte sind in normaler Schaltung wenn sich die Flüssigk...

Страница 8: ...PE 65 32 30 20 23 13 10 6 3 PIPE 210 105 100 50 120 70 60 30 60 48 30 20 4 PIPE 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 6 PIPE 950 475 450 220 550 375 260 180 375 265 180 130 260 200 120 90 130 100 60 50 8 PIPE 1550 850 730 400 1100 700 520 330 725 500 340 240 500 400 240 190 310 250 150 120 10 PIPE 2400 1300 1100 600 1850 1200 870 570 1200 850 570 400 875 700 410 330 650 525 310 25...

Страница 9: ...ériels et systèmes des dommages du à la diminution ou la perte de débit Installé dans des milliers de pipe line et d usine dans le monde entier Ce détecteur a actionnement magnétique donne d excellente performance Il n y a ni soufflet ressort ou joint pouvant provoquer des disfonctionnement la pale attire l aimant monté dans le corps et actionne le contact au moyen d un simple levier CARACTÉRISTIQ...

Страница 10: ...r Bornier Relais temporisé débit croissant Relais temporisé débit décroissant Application pour débit vertical vers le haut Bride de raccordement tuyauterie 2 2 1 2 3 4 Acier carbone Inox 316 Monel Hastelloy B Hastelloy C 150 LBS 300 LBS 600 LBS 900 LBS Raccordement avec pièce fileté sur tuyauterie 2 2 1 2 4 Hexagonal Affleurant Laiton Acier carbone Inox 316 Inox 304 Raccordement tuyauterie par Té ...

Страница 11: ...ions d utilisation et convenablement installé Le câble et le presse étoupe utilisés doivent tenir une température minimum de 80 C Connexion du presse étoupe Un scellement certifié EEx d approprié aux conditions d utilisations et correctement utilisé directement à l entrée du boîtier électrique Le scellement et le câble doivent tenir une température minimum de 80 C Note le détecteur est désactivé e...

Страница 12: ...8mm 2 65 32 30 20 23 13 10 6 Tuyau 76 2mm 3 210 105 100 50 120 70 60 30 60 48 30 20 Tuyau 101 6mm 4 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 Tuyau 152 4mm 6 950 475 450 220 550 375 260 180 375 265 180 130 260 200 120 90 130 100 60 50 Tuyau 203 2 mm 8 1550 850 730 400 1100 700 520 330 725 500 340 240 500 400 240 190 310 250 150 120 Tuyau 254 mm 10 2400 1300 1100 600 1850 1200 870 570 ...

Страница 13: ...camente para proteger a los equipos y sistemas de tuberias contra el daño producido por el aumento o descenso del caudal El V4 sobradamente probado se ha instalado en miles de tuberías y plantas de procesos en todo el mundo El diseño único del contacto le confiere una actuación superior No existen muelles resortes o sellos que se puedan romper En su lugar una paleta de libre movimiento atrae a un ...

Страница 14: ...Conexión soldada Conexiones eléctricas en un bloque terminal Relé de retardo de actuación en descenso de caudal Relé de retardo de actuación en ascenso de caudal Aplicaciones verticales Conexión a proceso bridada 2 2 1 2 3 4 Acero carbono 316 SS Monel Hastelloy B Hastelloy C 150 300 600 900 Conexion a proceso del casquillo 2 2 1 2 4 Hexagonal Superficial Latón Acero carbono 316 SS 304 SS Conexión ...

Страница 15: ...ra minima de 80 C Conexión del conducto Para la entrada del alojamiento eléctrico se debe suministrar un mecanismo de cierre EEx d con componentes adecuados para las condiciones de uso y correctamente instalados Nota El interruptor se desactiva y los contactos estan en condicion normal cuando no haya caudal en la linea 4 Asegurarse que las conductos o cables están correctamente sellados Los compon...

Страница 16: ...0 190 310 250 150 120 Tuberia 10 2400 1300 1100 600 1850 1200 870 570 1200 850 570 400 875 700 410 330 650 525 310 250 Tuberia 12 3450 1900 1600 900 2700 1750 1300 800 1850 1300 870 610 1250 1000 590 470 1000 800 470 380 Tuberia 20 10000 5500 4700 2600 7400 4800 3500 2300 5300 3700 2500 1700 3900 3100 1800 1500 3550 2850 1700 1300 Tuberia 18 8000 4400 3800 2100 6000 3900 2800 1800 4300 3000 2000 1...

Отзывы: