Dwyer Instruments UiM Coolpoint CP Series Скачать руководство пользователя страница 6

Configuring the solid state relay as alarm output:

1.  Make sure the meter is in “flow” display mode. The MENU push button is used to 

    toggle between the “flow” and “temperature” displays. When in “flow” mode, either 

    the GPM or the LPM LED lights up (both °F and °C LEDs will be off).

2.  Press and hold MENU.

3.  “FLo” is displayed, followed by either “PUL” (for pulse output) or “ALA” (for alarm 

    output).

4.   Release the MENU push button.

5.   If “ALA” is displayed, press the SET push button.

6.   If “PUL” is displayed, use the MENU push button to change it to “ALA”, then press 

    the SET button.

7.   The 3-digit value that is displayed is the alarm set point (as stored in the memory).

8.   Use the MENU button to change the alarm set point, if needed.

  

Note 1:

 When MENU is pressed once, the display increments to the next value. If 

    the MENU button is held down, the display will initially increment slowly, then 

    increment more quickly until the maximum allowed set point is reached. It will then 

    roll over to 0 and start from the minimum set point again. Please refer to Table 1 for 

    the range of acceptable flow set points for each flowmeter size.

  Note 2:

 When the set point is 0, the flow alarm is disabled.

9.   Press the SET push button to store the new set point in the memory.

10.The LED then displays either “nc” (normally-closed) or “no” (normally-open). This 

    is the state of the relay when there is no flow alarm.

11. Use the MENU push button to toggle between “nc” and “no”.

12. Use the SET push button to store the new relay configuration in memory.

Alarm Relays and Pulse Output

Both CP and CT models can be configured by the user to transmit either a flow alarm 

signal or a scaled-pulse output. An internal solid-state relay (SSR) is shared between 

the flow alarm and pulse output. 

Model CT has an additional SSR (independent of flow) for transmitting the temperature 

alarm.

The user menu is entered by pressing (and holding) the MENU push button. In this 

mode,  all  subsequent  selections  must  be  made  within  5  seconds  of  each  other. A 

period of inactivity (not touching the push buttons) longer than 5 seconds results in 

the meter’s reverting back to normal run mode, without storing the new selection in 

the memory.

Note:

 The “LSP” and “HSP” relay contacts are independent of each other and can be 

set to “nc” or “no” for the flow alarms. When either or both of the alarms are on, the 

alarm LED will blink.

Configuring the solid state relay as pulse output:

In order to configure the flowmeter for scaled-pulse output, proceed as follows:

1.  Make sure the meter is in “flow” display mode. The MENU push button is used to 

    toggle between the “flow” and “temperature” displays. When in “flow” mode, either 

    the GPM or the LPM LED lights up (both °F and °C LEDs will be off).

2.   Press and hold MENU.

3.   “FLo” is displayed, followed by either “PUL” (for pulse output) or “ALA” (for alarm 

    output).

4.   Release the MENU push button.

5.   If “PUL” is displayed, press the SET push button.

6.   If “ALA” is displayed, use the MENU push button to change it to “PUL”, then press 

    the SET button.

Pulse Output:

 There is an output pulse proportional to flow “rate” as well. The pulse 

output always indicates flow in GPM. It is driven by an internal solid-state relay with a 

10K pull-up resistor to supply voltage (pulse width = 3 msec). It should be noted that 

the pulse output represents instantaneous flow rate, not an averaged value. Therefore, 

flow jitter may be present when an external rate indicator is used, unless the indicator 

is capable of filtering or signal averaging.

The totalizer resolution and the corresponding flow rate pulse output depend on the 

full-scale setting of the flowmeter, as follows:

Configuring the Temperature Alarm

Only  model  CT  can  be  configured  by  the  user  to  transmit  a  temperature  alarm. 

An  internal  solid-state  relay  (independent  of  flow)  is  used  as  a  “high  alarm”  for 

temperature, meaning that the alarm signal is transmitted when the temperature set 

point is exceeded.

In order to configure the temperature alarm output, proceed as follows:

1.  Make sure the meter is in “temperature” display mode. The MENU push button is 

    used to toggle between the “flow” and “temperature” displays. When in 

    “temperature” mode, either the °F or the °C LED lights up (both GPM and LPM 

    LEDs will be off).

2.   Press and hold MENU.

3.   “t” is displayed, followed by “AL”.

4.   Release the MENU push button.

5.   The 3-digit value that is displayed is the alarm set point (as stored in the memory).

6.   Use the MENU button to change the alarm set point, if needed.

  Note 1:

 When MENU is pressed once, the display increments to the next value. If 

    the MENU button is held down, the display will initially increment slowly, then 

    increment more quickly until the maximum allowed set point is reached. It will then 

    roll over to 0 and start from the minimum set point again. Please refer to Table 2 for 

    the range of acceptable temperature set points.

  Note 2:

 When the set point is 0, the temperature alarm is disabled.

7.  Press the SET push button to store the new set point in the memory.

  Note:

 The state of the SSR (“nc” - normally-closed) or (“no” - normally-open) is 

    the same as the flow alarm relay, and can only be changed in the flow alarm menu, 

    regardless of whether the meter is configured for flow alarm or flow pulse output. In 

    other words, in order to select “no” or “nc” for temperature alarm relay, you must 

    repeat Steps 1-12 under “Configuring the Flow Alarm”. Later, if the meter is re-

    configured for scaled-pulse output (flow), it does not affect the temperature relay  

    state.

Содержание UiM Coolpoint CP Series

Страница 1: ...onal Temperature Limits 35 to 210 F 2 to 99 C Pressure Limits 10 to 300 psig 0 7 to 20 7 bar CP flange and CX 200 psig 20 7 bar max Response Time 450 ms Power Requirements 10 30 VDC 80 mA standard 25 mA for 2 wire option CP V8 2 AA alkaline batteries not included 45 day battery life Output 4 20 mA 100 pulses per gallon 3 wire models only 2 3 and 4 25 pulses per gallon Deadband Alarm output 2 5 FS ...

Страница 2: ...282 57 11 1 8 282 57 7 1 2 190 5 5 47 64 146 7 1 2 190 5 CP32 CT32 10 3 4 273 05 5 3 5 136 65 9 15 32 240 12 37 64 319 48 12 37 64 319 48 9 228 6 6 7 16 163 51 9 228 6 CP2 CP3 CP4 C3 Conduit box 3 1 4 82 55 1 11 64 41 15 5 13 32 137 16 4 5 64 103 38 2 15 64 59 44 6 13 32 162 81 CN6 CN8 4 1 2 114 3 2 1 4 57 15 5 11 16 144 53 4 39 64 116 84 2 3 4 69 85 6 51 64 172 47 CP6 CP8 4 1 2 114 3 2 1 4 57 15 ...

Страница 3: ...operated Material M1 M2 M5 M7 M8 Brass 316 SS Polysulfone Brass with nylon endcaps Brass with nylon hosebarbs Process Connection T1 T2 T3 T6 NPT female BSPT BSPP NPT male Electrical Connection C1 C2 C3 C7 C14 Male 5 pin 3 wire pig tail leads 3 3 ft 1 m Aluminum conduit box 3 wire pig tail leads with PG7 connector 3 3 ft 1 m 316 SS conduit box Output and Display D1 D3 D4E10 D4E1 4 20 mA output with...

Страница 4: ...ts to discuss the back pressure requirements Electrical Connections Totalizer with pulse output The unit shall be supplied by a Class 2 or SELV safety extra low voltage source in accordance with CSA C22 4 No 61010 1 012 Failure to do so may result in equipment damage CAUTION 1 2 3 4 5 4 20 mA FLOW SIGNAL OUT 24 VDC SUPPLY FLOW RELAY CONTACT FLOW RELAY CONTACT SUPPLY GROUND WHITE BROWN GRAY BLACK B...

Страница 5: ...0 6 1 2 3 7 5 15 30 40 80 1 5 2 3 4 5 11 30 56 113 151 302 3 6 12 22 5 45 90 180 280 560 12 23 45 85 170 341 682 1059 2119 0 1 1 2 2 5 5 10 15 30 0 4 5 9 18 37 57 114 TEMPERATURE SET POINT RANGES Meter Size Setpoint Min Setpoint Max Hysteresis F C F C F C All CT Models 35 1 200 93 4 2 SETUP AND CONFIGURATION Factory Default Settings Flow Units GPM Set Point 00 0 NO NC is set to NC Flow averaging f...

Страница 6: ... in flow mode either the GPM or the LPM LED lights up both F and C LEDs will be off 2 Press and hold MENU 3 FLo is displayed followed by either PUL for pulse output or ALA for alarm output 4 Release the MENU push button 5 If PUL is displayed press the SET push button 6 If ALA is displayed use the MENU push button to change it to PUL then press the SET button Pulse Output There is an output pulse p...

Страница 7: ...er installation RESPONSE TIME VS FILTER VALUE Filter Value Response Time S 2 4 8 16 32 0 9 1 4 2 3 4 7 5 MAINTENANCE REPAIR Upon final installation of the Series CP CN CT CX no routine maintenance is required The Series CP CN CT CX is not field serviceable and is not possible to repair the unit Field repair should not be attempted and may void warranty WARRANTY RETURN Refer to Terms and Conditions...

Страница 8: ..._____ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ____________________________________________________________________________________________________________________...

Отзывы: