Dwyer Instruments TUF series Скачать руководство пользователя страница 1

Series TUF Ultrasonic Energy Meter with BACnet Communication

Specifications - Installation and Operating Instructions

Bulletin F-TUF-B

The  

Series TUF Ultrasonic Energy Meter

 is a highly accurate and stable energy 

meter that utilizes ultrasonic technology to measure heating and cooling energy 

consumption.  The  Series  TUF  is  a  compact  meter  with  a  flowmeter  and  energy  

calculator in one, making it great for installation on chillers and boilers.

FEATURES/BENEFITS

• Lower maintenance costs with local parameter display and no moving parts

• Serial communication output allows for easy transfer of data

• Flow and temperature monitor in one unit eliminates the need for multiple units

APPLICATIONS

• Heat metering

• Utilities billing

• Tenant billing

• Monitoring of water heating or cooling: radiators, fan coils

INSTRUCTIONS FOR ORDERING

• Choose 1 ultrasonic energy meter model

• Choose 2 pipe fitting models given the appropriate fitting size (for DN15 to DN40 

 only)*

Example: 

TUF-150-MD,  Fitting  Size: A,  select  pipe  fitting  Model  WM-ACC-C01  or  

WM-ACC-C11.

SPECIFICATIONS

Service: 

Clean, compatible liquids.

Wetted Materials: 

Brass and 316L SS.

Range: 

See chart.

Display: 

8-digit LED.

Accuracy: 

BTU: EN1434/CJ128 

Class 2; Flow: ±(2+(0.02 Qp / Q))%; 

Temperature: ±0.1°C .

Power Requirements: 

24 VAC/VDC  

(model dependent)* or 3.6 V ER26500 

lithium metal battery, user supplied 

and installed, battery acts as back-up if 

power is lost.

Power Consumption: 

1 W.

Temperature Limits: 

Ambient: 41 to 

131°F (5 to 55°C); Process: 36 to 203°F 

(2 to 95°C).

Humidity Limit: 

< 93%.

Pressure Limits:

 232 psi (16 bar) for 

DN15 to DN40; 362 psi (25 bar) for 

>DN50.

Pressure Drop: 

< 1.5 psi (10 kPa).

Process Connection: 

See chart.

Serial Communications: 

Modbus

®

 RTU 

or BACnet MSTP (model selectable)**.

Enclosure Rating: 

IP65.

Enclosure Material: 

Plastic.

Repeatability: 

Flowmeter: 1%.

Electrical Connections: 

3 ft (0.91 m) 

4x0.2 mm2 cable with terminal block.

Flow Direction: 

Unidirectional.

Mounting Orientation: 

Horizontal or 

vertical.

Weight:

 See chart.

Agency Approvals: 

CE.

*Model numbers ending in “-DC” are for DC only applications.

**M-BUS available upon request.

Model

Dimensions in [mm]

Flow Rate GPM [LPM]

Weight

lb [kg]

L

D

H

Max Flow

(Qs)

Nominal Flow 

Range (Qp)

Min Flow

(Qi)

TUF-150-XX

TUF-200-XX

TUF-250-XX

TUF-320-XX

TUF-400-XX

4-21/64 [110.00]

5-1/8 [130.00]

6-19/64 [160.00]

7-3/32 [180.00]

7-7/8 [200.00]

G3/4B

G1B

G11/4B

G11/2B

G2B

3-31/32 [101.00]

3-31/32 [101.00]

4-11/64 [106.00]

4-29/64 [113.00]

4-49/64 [121.00]

13 [50]

22 [83]

31 [117]

53 [200]

88 [333]

6.6 [25]

11 [42]

15 [58]

26 [100]

44 [167]

0.1 [0.5]

0.2 [0.8]

0.3 [1.2]

0.5 [2]

0.9 [3.3]

3.1 [1.4]

3.1 [1.4]

4.1 [1.8]

5.2 [2.3]

6.6 [3.0]

Model

Dimensions in [mm]

Flow Rate GPM [LPM]

Weight

lb [kg]

L

ØD

H

ØD1

ØD2

N

Max Flow

(Qs)

Nominal Flow 

Range (Qp)

Min Flow

(Qi)

TUF-500-XX 

TUF-650-XX

TUF-800-XX

TUF-1000-XX

TUF-1250-XX

TUF-1500-XX

TUF-2000-XX

11-13/16 [300.00]

11-13/16 [300.00]

13-25/32 [350.00]

13-25/32 [350.00]

13-25/32 [350.00]

11-13/16 [300.00]

11-13/16 [350.00]

6-1/2 [165.00]

7-9/32 [185.00]

7-7/8 [200.00]

8-21/32 [220.00]

9-27/32 [250.00]

11-7/32 [285.00]

13-25/64 [340.00]

6-57/64 [175.00]

7-23/32 [196.00]

8-1/2 [216.00]

9-11/64 [233.00]

10-25/64 [264.00]

11-29/64 [291.00]

13-21/32 [347.00]

4-59/64 [125.00]

5-45/64 [145.00]

6-19/64 [160.00]

7-3/32 [180.00]

8-17/64 [210.00]

9-29/64 [240.00]

11-39/64 [295.00]

45/64 [18.00]

45/64 [18.00]

45/64 [18.00]

45/64 [18.00]

45/64 [18.00]

55/64 [22.00]

55/64 [22.00]

4

4

8

8

8

8

12

132 [500]

220 [833]

352 [1333]

528 [2000]

881 [3333]

1321 [5000]

2202 [8333]

66 [250]

110 [417]

176 [667]

264 [1000]

440 [1667]

660 [2500]

1101 [4167]

0.7 [2.5]

1.1 [4.2]

1.8 [6.7]

2.6 [10]

4.4 [17]

6.6 [25]

11 [42]

30.8 [14]

30.2 [13.7]

37.5 [17]

41.8 [19]

57.3 [26]

70.5 [32]

141 [64]

MODEL CHART

Model

Process 

Connection

Corresponding Pipe 

Fitting

Power

Model

Process 

Connection

Corresponding Pipe 

Fitting

Power

TUF-150-XX

TUF-200-XX

TUF-250-XX

TUF-320-XX

TUF-400-XX

TUF-500-XX

TUF-650-XX

TUF-800-XX

TUF-1000-XX

TUF-1250-XX

G-3/4

G1

G1-1/4

G1-1/2

G2

GB9119 flange

GB9119 flange

GB9119 flange

GB9119 flange

GB9119 flange

1/2˝ NPT or BSPT

3/4˝ NPT or BSPT

1˝ NPT or BSPT

1-1/4˝ NPT or BSPT

1-1/2˝ NPT or BSPT

2˝ DN 50 PN 16 flange

2-1/2˝ DN 65 flange

3˝ DN 80 flange

4˝ DN 100 flange

5˝ DN 125 flange

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

24 VAC/VDC

TUF-150-XX-DC

TUF-200-XX-DC

TUF-250-XX-DC

TUF-320-XX-DC

TUF-400-XX-DC

TUF-500-XX-DC

TUF-650-XX-DC

TUF-800-XX-DC

TUF-1000-XX-DC

TUF-1250-XX-DC

G-3/4

G1

G1-1/4

G1-1/2

G2

GB9119 flange

GB9119 flange

GB9119 flange

GB9119 flange

GB9119 flange

1/2˝ NPT or BSPT

3/4˝ NPT or BSPT

1˝ NPT or BSPT

1-1/4˝ NPT or BSPT

1-1/2˝ NPT or BSPT

2˝ DN 50 PN 16 flange

2-1/2˝ DN 65 flange

3˝ DN 80 flange

4˝ DN 100 flange

5˝ DN 125 flange

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

L

H

ØD

4´ RETURN PIPE TEMP SENSOR 

4´ 4-CORE WIRE

[2 COMMUNICATION, 2 POWER]

4´ FLOW PIPE TEMP SENSOR

2.8´ WATER-OUT FLOW SENSOR

2.8´ WATER-IN FLOW SENSOR

ØD2

 ´N´ NO. OF HOLES

[SEE TABLE] 

ØD1 B.C.

H

4-1/4

[108.00]

L

[2 COMMUNICATION, 2 POWER]

4´ RETURN PIPE TEMP SENSOR

2X D

THREAD

4´ FLOW PIPE TEMP SENSOR

2.8´ WATER-OUT

FLOW SENSOR  

2.8´ WATER-IN

FLOW SENSOR 

4´ 4-CORE WIRE

Modbus

®

 is a registered trademark of Schneider Automation, Inc.

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com
e-mail: [email protected]

®

Содержание TUF series

Страница 1: ... 2 0 9 3 3 3 1 1 4 3 1 1 4 4 1 1 8 5 2 2 3 6 6 3 0 Model Dimensions in mm Flow Rate GPM LPM Weight lb kg L ØD H ØD1 ØD2 N Max Flow Qs Nominal Flow Range Qp Min Flow Qi TUF 500 XX TUF 650 XX TUF 800 XX TUF 1000 XX TUF 1250 XX TUF 1500 XX TUF 2000 XX 11 13 16 300 00 11 13 16 300 00 13 25 32 350 00 13 25 32 350 00 13 25 32 350 00 11 13 16 300 00 11 13 16 350 00 6 1 2 165 00 7 9 32 185 00 7 7 8 200 00...

Страница 2: ... Analog value object AV0 through AV4 are for viewing additional information such as meter mode balance sheet and time The object property table for the analog value objects with appropriate units and formats can be found in Appendix III and IV ADDITIONAL NOTES 1 The communication write status features a power off save where the last communicated information will be saved upon powering off the unit...

Страница 3: ...le C and D are the improper positions 3 If the meter is installed on the horizontal pipe it must be oriented at least 45 from horizontal see Figure 4 If the meter s face is horizontal then debris accumulation can increase inaccuracies see figure 5 for correct and incorrect orientations There is no special requirement when installing on the vertical pipe work Note the meter can be installed on the ...

Страница 4: ...ing down the button for 1s will switch the sections from curren information to monthly information and then to other information Once in the desired section pressing the key will switch the information shown for the given section 2 Display Units Energy is displayed in kW h power is displayed in kW flow volume is displayed as m3 and flow rate is displayed in m3 h 3 Display Details a Monthly Reading...

Страница 5: ...of flow rate 1 History reading date 2 History reading energy 2 Sum of flow rate 2 Hold button Hold button Current Information Monthly Information Other Information Error 4 message Error 4 beginning time Error 4 ending time Battery voltage Secondary address Primary address Protocol version LCD segment test Sum of current working time Current Hour minute second Current Year month date Error 1 messag...

Страница 6: ...01 Ultrasonic BTU Meter DEVICE 8 Operation 0 Dwyer Instruments Inc 607 TUF XX BN X X X X Basic Protocol Converter 1 5 Read Property write property who is Analog Input Analog Value Device See Table on page 3 50 NO_SEGMENTS 3 BACnetObjectIdentifier CharacterString 32 BACnetObjectiveType BACnet Device Status CharacterString Unsigned CharacterString CharacterString CharacterString CharacterString 32 U...

Страница 7: ...bjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits Read Read Read Read Read Read Read APPENDIX II ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access Object Identifier Object Name Object Type Present Value Status Flags Event State Units AI6 Total Heat ANALOG_INPUT 0 Current Reading 0 NORMAL 0 Kilowatt hours 19 BACnetObjectIdentifier CharacterStr...

Страница 8: ...tObjectIdentifier CharacterString BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits Read Read Read Read Read Read Read APPENDIX III ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access Object Identifier Object Name Object Type Present Value Status Flags Event State Units AV4 TUF Address ANALOG_VALUE 2 127 0 NORMAL 0 No units 95 BACnetObj...

Отзывы: