Series CDTV Wall Mount Carbon Dioxide / Volatile 

Organic Compound Transmitter

Specifications - Installation and Operating Instructions

Bulletin AQ-CDTV-N

The 

SERIES CDTV

 Carbon Dioxide / Volatile Organic Compound (VOC) Transmitter 

reduces energy cost in buildings by lowering the amount of conditioned air based on 

the occupancy of the space. By detecting both CO

2

 and VOC, the transmitter can 

also detect fumes that may need to be exhausted during lower occupancy periods. 

Combining both measurements in one transmitter reduces both labor and material 

costs by only having to install one CDTV-VOC unit, instead of separate CO

2

 and VOC 

transmitters. 

Carbon dioxide measurements are taken using our proven Single-Beam Dual-

Wavelength Non-Dispersive Infrared (NDIR) sensor. Our sensor allows users to get 

accurate measurements without waiting for the settling / correction periods of other 

logic based sensors. Transmitters can be used in buildings and applications that have 

24 hour occupancy and can be calibrated on site to match environmental conditions 

for improved accuracy. 

The VOC measurement is a single value derived from the presence of substances 

including alcohols, aldehydes, aliphatic hydrocarbons, amines, aromatic hydrocarbons, 

CO, CH4, LPG, ketones, and organic acids. Although a standard unit of measure is 

not currently defined, the VOC measurement unit “ppm CO

2

 equivalent” used by the 

device is commonly used in the industry. The VOC measurement does not actually 

measure CO

2

, but instead senses and indicates an air quality value that approximately 

correlates perceived comfort levels to similar concentrations of CO

2

 in the environment. 

Single-beam dual-wavelength sensor advantages: 

•  Automatically corrects for aging effects in occupied and unoccupied buildings

    •  Perfect for hospitals and manufacturing plants that are occupied 24 hours per  

   day

•  Measures actual unfiltered light intensity directly

    •  Eliminates error from incorrect assumptions of gas concentration in theoretical  

   logic assumption methods...

SPECIFICATIONS

Range: 

CO

2

: 0 to 2000 or 0 to 5000

 

ppm (depending on model); VOC: 0 to 2000 

ppm CO

2

 equivalent.

Accuracy: 

CO

2

: ±40 ppm +3% of reading.

Temperature Dependence: 

±8 ppm / °C at 1100 ppm.

Non-Linearity:

 CO

2

: 16 ppm.

Pressure Dependence: 

CO

2

: 0.13% of reading per mm of Hg.

Response Time: 

CO

2

: 2 minutes for 99% step change; VOC: 5 minutes.

Temperature Limits: 

32 to 122°F (0 to 50°C).

Power Requirements: 

16 to 35 VDC / 19 to 28 VAC.

Power Consumption: 

Average: 2 watts; Peak: 3.75 watts.

Sensor: 

CO

2

: Single-beam, dual-wavelength NDIR; VOC: MEMS metal oxide 

semiconductor

.

Output: 

Current: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, or 2 to 10 mA (depending on

selection jumper, max 500 Ω); Voltage: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, or 1 to 

5 VDC (depending on selection jumper, min 500 Ω); Relay: SPST NO 2A @ 30 VDC.

Weight: 

4.4 oz (125 g).

Agency Approvals: 

CE.

1.10

[27.96]

3.000

[76.20]

.552

[14.02]

2x .176

[4.47]

.573

[14.56]

4.50

[114.30]

2.80

[71.12]

®

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com