The Series RHP-W Wall Mount Humidity/Temperature/Dew Point Transmitter

is  the  most  versatile  room  transmitter  on  the  market. The  stylish  housing  is  well
vented to provide air flow across the sensor to improve measurement accuracy. An
optional LCD display can be integral to the transmitter or a remote display can be
ordered for building balancing or LEED validation. The LCD display indicates the
ambient  temperature  along  with  the  humidity  or  dew  point.  The  transmitter  has
internal dip switches to select the temperature engineering units and whether the
transmitter outputs humidity or dew point.
The humidity and temperature sensors are field replaceable to reduce service cost
and inventory. The humidity and the dew point are measured using a capacitive
polymer sensor that completely recovers from 100% saturation. The humidity and
dew point can have either a current or voltage output, while the optional tempera-
ture output can be a current, voltage, RTD or thermistor. For models with current
or voltage for the temperature output, the temperature range is field selectable.

INSTALLATION

Series RHP-W Wall Mount Humidity/Temperature/Dew Point Transmitter

Specifications - Installation and Operating Instructions

Bulletin H-RHP-W

SPECIFICATIONS
Relative Humidity Range: 

0 to 100% RH.

Temperature Range: 

-40 to 140°F (-40 to 60°C) for thermistor and RTD sensors. 

-20 to 140°F (-28.9 to 60°C) for solid state temperature sensors.

Dew Point Temperature Range: 

-20 to 140°F (-28.9 to 60°C); 0 to 100°F 

(-17.8 to 37.8°C); 40 to 90°F (4.4 to 32.3°C); -4 to 140°F (-20 to 60°C) field selec-
table ranges.

Accuracy: 

RH: 

Model RHP2 ±2% 10-90% RH @ 25°C; Model RHP3 ±3% 20-80% RH @ 

25°C.

Thermistor Temperature Sensor: 

±0.4°F @ 77°F (±0.22°C @ 25°C).

RTD Temperature Sensor: 

DIN Class B; ±0.54°F @ 32°F (±0.3°C @ 0°C).

Solid State Temperature Sensor: 

±0.9°F @ 72°F (±0.3°C @ 25°C).

Hysteresis: 

±1%.

Repeatability: 

±0.1% typical.

Temperature Limits: 

-40 to 140°F (-40 to 60°C).

Storage Temperature: 

-40 to 176°F (-40 to 80°C).

Compensated Temperature Range: 

-4 to 140°F (-20 to 60°C).

4-20 mA Loop Powered Models:

Power Requirements:

10-35 VDC.

Output Signal:

4-20 mA, 2 channels for humidity/solid state temperature sensor  

models (loop powered on RH). Switch selectable RH/dew point. Switch 
selectable normal or reverse output.

0-5/10V Output Models:

Power Requirements:

15-35 VDC or 15-29 VAC.

Output Load:

5 mA max., 2 channels for humidity/solid state temperature 

sensor models. Switch selectable 0-10V/2-10V or 0-5V/1-5V output. Switch 
selectable RH/dew point. Switch selectable normal or reverse output.

Solid State Temperature Sensor Output Ranges: 

Switch selectable, 

-20 to 140°F (-28.9 to 60°C); 0 to 100°F (-17.8 to 37.8°C); 40 to 90°F 
(4.4 to 32.3°C); -4 to 140°F (-20 to 60°C).

Response Time: 

15 seconds.

Electrical Connections: 

Screw terminal block.

Drift: 

<1% RH/year.

RH Sensor: 

Capacitance polymer.

Enclosure Material: 

White polycarbonate.

Display: 

Optional LCD, backlit on 0-5/10V models. Switch selectable %RH or dew

point, °F/°C.

Display Resolution: 

RH: 1%; Temperature: 0.1°F (0.1°C); Dew Point: 1°F (1°C).

Weight: 

0.3 lb (0.14 kg).

Agency Approvals: 

CE.

1-3/16

[30.16]

1-3/16

[30.16]

.921

3x 3/8
[9.53]

35/64

[13.89]

1-13/32

[35.72]

1-53/64

[46.43]

4x 3/16

[4.76]

1-13/32

[50.01]

4-31/64

[113.9]

3-13/32

[86.52]

Shown with optional LCD display

Do  not  exceed  ratings  of  this  device,  permanent  damage  not
covered by warranty may result. The 4-20 mA models are  not

designed for AC voltage operation.

CAUTION

Avoid  locations  where  severe  shock  or  vibration,  excessive
moisture or corrosive fumes are present.

CAUTION

Use  electrostatic  discharge  precautions  (e.g.,  use  of  wrist
straps) during installation and wiring to prevent equipment dam-

age.

CAUTION

Disconnect power supply before installation to prevent electrical
shock and equipment damage.

Make  sure  all  connections  are  in  accordance  with  the  job  wiring  diagram  and  in
accordance with national and local electrical codes. Use copper conductors only.

WARNING

www.

.com

[email protected]

1.800.561.8187