Series DM-2000 Differential Pressure Transmitter 

Specifications - Installation and Operating Instructions

Bulletin E-43-DM

The 

Dwyer Series DM-2000 Differential Pressure Transmitter 

senses the pressure 

of air and compatible gases and sends a standard 4-20 mA output signal. The DM-

2000  housing  is  specifically  designed  to  mount  in  the  same  diameter  cutout  as  a 

standard Magnehelic

®

 differential gage. A wide range of models are available factory 

calibrated to specific ranges.

Pressure connections are inherent to the glass filled plastic molded housing making 

installation quick and easy. Digital push-button zero  simplifies calibration over typical 

turn-potentiometers. Single push button allows field selection of 5 engineering units 

(LCD models only). An optional 3.5 digit LCD shows process and engineering. 

Accessories

Mounting Lugs

6-20 x 2˝ Screws - 3

6-19 x 1/2˝ Screws - 3

INSTALLATION

  1. Location

  Select a clean, dry mounting location free from excess vibration where the  

 

  temperature will remain between 20 and 120˚F (-6.7 and 48.9˚C). Distance from the 

  receiver is limited only by total loop resistance. See Electrical Connections on next 

  page. The tubing supplying pressure to the instrument can be practically any length 

  required, but long lengths will increase response time slightly.

  2. Position

  A vertical position required. That is the position in which all standard models are  

  spanned and zeroed at the factory.

Pressure Connections

Two integral tubing connections are provided on the side of the gage. They are sized 

to fit 1/8˝ (3.12 mm) I.D. tubing. Be sure the pressure rating of the tubing exceeds that 

of the operating ranges.  

Note: 

The tubing connections on the back of the gage are not to be used as process 

connections.

  3. Mounting

  Panel - Provide a 4-9/16˝ diameter opening in panel. Insert gage and secure in place 

  with provided screws and adapters.

  Surface - Provide three 3/16˝ diameter holes in panel on a 4-1/8˝ diameter bolt circle. 

  Cut opening for terminal block as shown in diagram to right.

SPECIFICATIONS

Service:

 Air and non-combustible, compatible gases.

Wetted Materials:

 Consult Factory.

Accuracy: 

±1% F.S. at 70°F.

Stability:

 ±1% F.S./yr.

Temperature Limits:

 20 to 120°F (-6.67 to 48.9°C).

Pressure Limits:

 10 psig (0.69 bar).

Thermal Effect:

 ±0.055% F.S./°F (0.099% F.S./°C).

Power Requirements:

 10-35 VDC (2 wire).

Output Signal:

 4 to 20 mA.

Zero and Span Adjustments: 

Digital push-button zero and span.

Loop Resistance:

 DC: 0-1250 ohms maximum.  

Current Consumption: 

DC: 38 mA maximum.   

Electrical Connections: 

Screw-type terminal block.

Process Connections: 

1/8˝ I.D. tubing.

Mounting Orientation: 

Vertical.

Weight:

 4.8 oz (136 g).

HIGH PRESSURE PORT

1-1/4

[31.75]

7/16

[11.11]

17/32

[13.50]

1-11/16

[42.86]

5/32

[3.97]

ø4-3/4

[120.65]

LOW PRESSURE PORT

1

(25.40)

11/16

(17.46)

65.000°

(3) HOLES FOR #6 SCREW

EQUALLY SPACED ON

4-1/8 (104.78) B.C.

1-1/2

(38.10)

1

(25.40)

11/16

(17.46)

65.000°

(3) HOLES FOR #6 SCREW

EQUALLY SPACED ON

4-1/8 (104.78) B.C.

1-1/2

(38.10)

Surface

Panel

®