Dwyer Instruments DCT500ADC Series Скачать руководство пользователя страница 1

Series DCT500ADC Timer Controller

Specifications - Installation and Operating Instructions

Bulletin E-98ADC

The 

Series DCT500ADC Timer Controller 

is a timing system for pulse-jet type 

dust collectors or pneumatic conveying systems in either continuous or on-demand 

cleaning applications. It is provided with either 4, 6, or 10 channels. The DCT500ADC 

was designed for ease of installation in your dust collector system. For installations 

requiring fewer channels than available on the board, a shorting plug is provided to 

allow selection of the last used channel. Time-on and time-off settings are selected 

using two potentiometers. High-limit and low-limit control inputs are provided for use 

with on-demand systems. When used in a continuous mode the high-limit input is 

jumpered. 

Installation

Warning:  Always replace the fuse with the proper type and rating. 

 

The fuse is Type 3 AG fast acting 3 Amp @ 250V.  DO NOT use slow-

blow type fuses. Failure to comply with this requirement will void 

manufacturer’s warranty.

This equipment is intended to be powered using a recognized Class 2 

power supply. If powered from a DC bus a suitable transient protection 

device meeting Installation Category II requirements must be used. 

Protection provided by the equipment may be impaired if the equipment 

is used with accessories not provided or recommended by the 

manufacturer, or is used in a manner not specified by the manufacturer.

Power Requirements

The DCT500ADC Series controller is designed for operation with a DC power supply. 

The supply voltage must be between 10 VDC and 35 VDC. Exceeding 35 VDC may 

damage the unit. The solenoid outputs are driven from the power supply so the 

solenoids must be rated for operation at the power supply voltage.  The solenoids 

are connected as shown in the wiring diagram and must not be connected to any 

other external circuit. The solenoid common is the positive (+) lead and is internally 

connected to the fused positive (+) supply. The individual outputs are switched to 

the negative (-) supply input through an open drain field effect transistor (FET). The 

outputs are protected for inductive flyback transients of the solenoids.

Location

The system must be located in an enclosure that meets relevant safety standards and 

electrical codes. There are no other special orientation requirements. Mount it using 

the four mounting holes in the baseplate. The baseplate back is flush, so no special 

spacers are needed to accommodate obstructions except for those imposed by the 

location itself. 

Connections

The power and solenoid connections are located at the lower edge of the board. 

The terminal block is a “Euro” style connector system that clamps the wire within the 

connector body. The connector will accept wire sizes from 14 to 22 gages. These 

terminals  should  be  torqued  to  5  in.  lb.  The  connectors  are  specified  for  single 

connection but multiple wires may be connected to a single lug provided local codes 

allow this and good workmanship practices are followed. When using stranded wire, 

make  sure  that  there  are  no  “stray”  strands.  These  may  cause  system  failure  or 

damage.  Connect the (+) (-) power to (+) and (-). Connect the solenoids between the 

selected output and the solenoid common. Solenoid common and (+) are internally 

connected through fuse.  Refer to Figure 2-1.

The wire should be stripped to no more than 0.25 in. A strip gauge is provided at 

the lower right corner of the board. Longer than this may cause shorts. Switches 

connected to the control inputs at the top of the board must be isolated normally open 

contacts connected only to the relevant terminal and to the common terminals. 

The following subparagraphs describe the external switch connections. Refer to figure 

2-1 for switch connection illustration.

SPECIFICATIONS

Output Channels:

 4, 6, and 10 channels.

Voltage Requirements:

 10 to 35 VDC ( ). 

Power Consumption:

 0.6 W. 

Input Power:

 106 W @ 35 VDC ( ) max.

Load:

 3A max per channel.

Fuse:

 Type 3 AG, 3A @ 250 VAC (~).

Ambient Operation Temperature:

 -40 to 149°F (-40 to 65°C).

Storage Temperature Limits:

 -40 to 176°F (-40 to 80°C).

Humidity Conditions:

 5 to 95% noncondensing.

On Time:

 50 to 500 msec.

On Time Accuracy:

 ±5% of setting.

On Time Repeatability:

 ±1 msec.

Off Time:

 1 to 180 seconds.

Off Time Accuracy:

 5% of setting.

Pollution Degree:

 2.

Altitude:

 6560 ft (2000 m) max.

Environment:

 Indoor use, must be installed in a weather-proof enclosure for 

outside applications.

Weight:

 9 oz (255 g).

Agency Approvals:

 CE.

 1/16

[1.59]

   1/2

[12.70]

1-3/16

[30.16]

  6-1/4 [158.75]

   6-3/4 [171.45]

  4-1/4

[107.95]

  4-7/8

[123.83]

®