Dwyer Instruments A3000 series Скачать руководство пользователя страница 1

INSTALLATION
1. Location: 

Select a clean, dry, vibration-free location where

ambient temperatures will be between 20 and 120°F (-6.67 and
48.9°C). Tubing supplying pressure to the instrument can be
practically any length but long runs will increase response time
slightly.

2. Position:

The PHOTOHELIC

® 

Switch/Gage is factory cali-

brated for use with scale in a vertical plane. Operation at other
angles may affect accuracy and/or require zero adjustment.
Most models can be specially calibrated at the factory for other
positions if specified at time of ordering. Ranges below 1

″ 

W.C.

must be used only with scale vertical.

3. Mounting: 

The PHOTOHELIC

® 

is normally mounted before

making electrical connections. The electrical enclosure is
removable at any time regardless of mounting method.

(A) Panel Mounting:

Normal mounting is flush or through panel

as shown in Fig. B. Allow 4-

3

/

8

(111.13 mm) clearance behind

the unit for removal of electrical enclosure. Make a 4-13/16

(122.24 mm) diameter hole in panel. Insert the PHOTOHELIC

®

unit from front of panel and slip mounting ring over case from
behind with stepped side facing rear. Fit the snap ring into nar-
row groove at back edge of the bezel. Thread four 6-32 x 1-1/4

mounting screws into tapped holes in mounting ring and seat it
against snap ring. Tighten screws against back of panel. See
Fig. B.

Series A3000 Photohelic

®

Differential Pressure Switch/Gage

Specifications - Installation and Operating Instructions

Bulletin B-33-A

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

Lit-By Fax: 888/891-4963 

The PHOTOHELIC

®

Series A3000

is a versatile 2-in-1 instru-

ment combining a time-proven Magnehelic

®

differential pres-

sure gage with low/high pressure switches. It is designed to
measure and control positive, negative or differential pressure
of air or other non-combustible, non-corrosive gases. Gage
reading is unaffected by switch operation. Switch set points are
easily adjusted with knobs located on gage face. Applied pres-
sure and switch set points are fully visible at all times.
Deadband is one pointer width, less than 1% of full scale. Each
set point controls a DPDT relay and both relays can be inter-
locked to provide variable deadband control.

SPECIFICATIONS

GAGE SPECIFICATIONS

Service: 

Air and non-combustible, compatible gases.

Wetted Materials: 

Consult Factory.

Accuracy: 

Photohelic

®

, ±2% of full scale at 70°F (21.1°C). ±3%

on -0 and ±4% on -00 models. Capsu-Photohelic

®

± 3% of full

scale at 70°F (21.1°C). ±2% on 43000S models; ±4% on 43215,
43220 and 43500.

Pressure Limits: 

Photohelic

®

-20" Hg. to 25 psig (-0.677 to 1.72

bar). MP  option; 35 psig (2.41 bar), HP option; 80 psig (5.52 bar).
36003S – 36010S; 150 psig (10.34 bar). 36020S and higher;1.2 x
full scale pressure. Capsu-Photohelic

®

,  -20Hg. To 500 psig (-

0.677 to 34.5 bar).

Temperature Limits: 

20° to 120°F. 

(-6.67° to 48.9°C) Low temperature option available. 

Process Connections: 

Photohelic

®

, 1/8˝ female NPT.  Capsu-

Photohelic

®

1/4˝ female NPT.  

Size: 

Photohelic

®

, 4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 8-

1/4˝ (209.55 mm). Capsu-Photohelic

®

, 4˝ (101.6 mm) dial face, 5˝

(127 mm) O.D. x 9-3/16” (233.36 mm).

Weight: 

Photohelic

®

, 4 lbs. (1.81 kg). Capsu-Photohelic

®

5 lbs., 8

oz. (2.49kg). Capsu-Photohelic

®

Brass 11 lbs., 2 oz. (5.05 kg).

SWITCH SPECIFICATIONS

Switch Type: 

Each setpoint has 2 Form C relays (DPDT).

Repeatability:  

±1% of full scale.

Electrical Rating: 

Photohelic

®

,  10A @ 28 VDC, 10A @ 120, 240

VAC; Capsu-Photohelic

®

10A @ 120 VAC, 6A  @ 240 VAC, 60

Hz res. 10A @ 28 VDC.

Electrical Connections: 

Screw Terminals.

Power Requirements: 

120 VAC, 50/60 Hz; 240 VAC & 24 VAC

Power optional.

Mounting Orientation: 

Diaphragm in vertical position. Consult

factory for other position orientations.

Set Point Adjustment: 

Adjustable knobs on face. 

Agency Approvals: 

Photohelic

®

UL: File No. E38121, Vol. 1,

Sec. 4; CSA: File No. LR22541-34; CE: EN 61000-6-2: 1999, EN
6100-3-2: 2000, EN 61000-3-3: 2000.

Ø4-13/16 [122.24]

HOLE REQUIRED FOR

PANEL MOUNTING

1/2 MALE NPT PRESSURE CONNECTION.

SINGLE HIGH PRESSURE CONNECTION

FOR SERIES 36000S MODELS.

SNAP RING GROOVE

Fig. A

Fig. B

NOTE:

Detailed dimension drawings are available from our Customer Service

Dept. for PHOTOHELIC

®

switch/gages as installed in two optional enclosures.

For weatherproof housing, request no. 13-700132-00. /For explosion-proof

housing, request no. 13-700113-01.

2-1/2 [63.50]

2-1/16 [52.39]

2 [50.80]

1-1/4

[31.75]

(4) 6-32 HOLES

EQUALLY SPACED ON

A 5-1/8 [130.18] B.C.

Ø4-47/64

[120.25]

Ø5

[127.00]

Ø4 [101.60]

FACE

5-1/2 [139.70] 

O.D.

MOUNTING 

RING

5/8 [15.88]

5/8 [15.88] PANEL 

MAX

3/16 [4.76]

3-7/8 [98.43]

5-1/8 [130.18]

6-3/8 [161.93]

(7-5/8 [193.68])

4-3/8 [111.13]

HOUSING REMOVAL

3/4 CONDUIT

CONNECTION

Ø4-3/4

[120.65]

3-7/8 SQ

[98.43]

1/8 FEMALE NPT HIGH 

PRESSURE CONNECTION

1/8 FEMALE NPT LOW

PRESSURE CONNECTION

B-33-A  11/12/02  4:36 PM  Page 1

Содержание A3000 series

Страница 1: ...e variable deadband control SPECIFICATIONS GAGE SPECIFICATIONS Service Air and non combustible compatible gases Wetted Materials Consult Factory Accuracy Photohelic 2 of full scale at 70 F 21 1 C 3 on 0 and 4 on 00 models Capsu Photohelic 3 of full scale at 70 F 21 1 C 2 on 43000S models 4 on 43215 43220 and 43500 Pressure Limits Photohelic 20 Hg to 25 psig 0 677 to 1 72 bar MP option 35 psig 2 41...

Страница 2: ...ressure taps to positive nega tive or differential pressure sensing points Use 1 4 diame ter metal or other instrument tubing and 1 8 NPT adapters at the PHOTOHELIC pressure switch gage Adapters for rubber or soft plastic tubing are furnished with the instru ment for use where this type of connection is preferred If the PHOTOHELIC is not used to sense differential pres sure one of the pressure tap...

Страница 3: ...e connected to Sections A and B of the terminal board The left or low set point components are omitted 4 Circuit Style The PHOTOHELIC is available with several factory installed optional internal circuits They are identified as to style by a label shown in Fig J This label is mounted prominently on the terminal board of each instrument The letter H denotes a circuit in which the relay can be made ...

Страница 4: ...Manual reset is accomplished by adding a normally closed reset switch or push button to the circuit as described in paragraph 6 above 11 Single Set Point Special Manual reset after actuation on falling pressure can be obtained by using Circuit Style SRL Consult the factory for special units and detailed instructions regarding their use 12 Placing in Service In normal operation each relay is de ene...

Отзывы: