Dwyer Instruments 490W Series Скачать руководство пользователя страница 1

Series 490W Hydronic Differential Pressure Manometer - 

Hydronic Application Software

Specifications - Installation and Operating Instructions

Bulletin TE-490W-QS

Series 490W Hydronic Differential Pressure Manometer

 is the most accurate 

and easy to operate manometer on the market. By using wireless transducers and 

a versatile handheld, a single operator can monitor and balance a hydronic system 

in less time than traditional hydronic balancers. The Series 490W utilizes mobile 

technology to communicate via a Bluetooth connection with the transducers to 

monitor differential pressure and flow on up to three different valves. Being wireless 

means there are no hoses to carry, snag on equipment or needing to be drained. The 

490W includes Dwyer’s Hydronic Application Software that contains valve charts for 

numerous manufacturers, which converts differential pressure to flow directly on the 

screen.

INCLUDED WITH THE 490W

  1. Handheld test instrument with Dwyer Hydronic App preloaded onto device

  2. Pressure transducers (4 per kit) with case

  3. Installation and operating manual

  4. 1/4˝ SAE 45° x 1/4˝ Male NPT straight adapter (2 per kit)

  5. 1/4” Female elbow x 1/4˝ Male NPT fitting (2 per kit)

  6. Piercing gauge adapters [2 per size] (6 per kit)

      -1/8˝ DIA x 1-1/2˝ length

      -1/8˝ DIA x 3˝ length

      -1/16˝ x 1-1/2˝ length

  7. 490W fabric carrying case

  8. Piercing gauge adapters and fittings case (2 per kit)

  9. Charger cable and power adapter for handheld test instrument

Gorilla

®

 is a registered trademark of Corning, Incorporated

SPECIFICATIONS

Wireless Distance:

 Up to 65´ (19.8 m).

Service:

 Compatible gases & liquids.

Wetted Materials:

 316 SS, PTFE, brass.

Accuracy:

 2% of reading, ±1 psi.

Compensated Temperature Range:

 14 to 140°F (-10 to 60°C).

Pressure Hysteresis:

 ±0.25% FS.

Pressure Range:

 See chart.

Process Temperature Limits:

 -4 to 185°F (-20 to 85°C).

Display:

 5˝ Gorrilla

®

 glass 3, touch screen, 1280x720.

Resolution:

 0.01 psi.

Process Connections:

 Two 1/4˝ male NPT.

Power Requirements:

 CR2050 or CR2032 lithium battery, user replaceable.

Weight:

 2 lb (907 g).

Agency Approvals:

 CE, FCC.

3-17/64 [83]

6-17/64

[159]

5/8

[16]

1.000

2.940

.944

HEX

MODEL CHART

Model

English Range

Metric Range

Maximum Range

Available Engineering Units

490W-6-HKIT/NIST

0 to 50 psi, 0 to 200 psi 0 to 344.7 kPa, 0 to 1379 kPa 100 psi (6.89 bar), 400 psi (27.58 bar) psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.

REPLACEMENT TRANSDUCERS

A-490W-1

A-490W-2

A-490W-3

A-490W-4

A-490W-5

A-490W-6

0 to 15 psi

0 to 30 psi

0 to 50 psi 

0 to 100 psi

0 to 500 psi

0 to 200 psi

1.034 bar

2.069 bar

3.447 bar

6.895 bar

34.47 bar

13.79 bar

30 psig

60 psig

100 psig

200 psig

1000 psig

400 psig

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. 

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. 

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. 

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. 

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. 

psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.

®

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com
e-mail: [email protected]

Содержание 490W Series

Страница 1: ...and power adapter for handheld test instrument Gorilla is a registered trademark of Corning Incorporated SPECIFICATIONS Wireless Distance Up to 65 19 8 m Service Compatible gases liquids Wetted Materials 316 SS PTFE brass Accuracy 2 of reading 1 psi Compensated Temperature Range 14 to 140 F 10 to 60 C Pressure Hysteresis 0 25 FS Pressure Range See chart Process Temperature Limits 4 to 185 F 20 to ...

Страница 2: ...up to 2 years depending on usage When transducers are sent in for annual recertification the battery will be replaced Battery life depends on its capacity operating temperature and signal transmission interval When battery replacement becomes necessary use only a CR2050 or CR2032 type such as a Sony CR2050W or CR2032W NOTICE When the 490W is received the handheld test instrument will only have a p...

Страница 3: ...cally go into low power sleep mode to conserve battery energy The transducers exit low power mode upon receiving communications from the Hydronic Application NOTICE Touch to start app Figure 2 Touch to select valve make and model Touch the NEXT button to proceed Dwyer Hydronic App Operation First turn on the handheld by pushing the power button See Figure 1 Once fully powered on unlock the handhel...

Страница 4: ... pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications However there is no guarantee that interference will not o...

Отзывы: