Series 490A Hydronic Differential Pressure Manometer

Bulletin D-24A

Specifications - Installation & Operating Instructions

SPECIFICATIONS
Service: 

Compatible gases & liquids.   

Wetted Materials: 

316 SS; -3V option: 316LSS, Buna-N, silicone, grease, PTFE,

brass 360, copper, reinforced acetal copolymer; -HKIT option: 316LSS, PTFE,
brass, copper.

Accuracy: 

±0.5% FS from 60 to 78°F (15.6 to 25.6°C); ±1.5% FS from 32 to 60°F

and 78 to 104°F (0 to 15.6°C and 25.6 to 40°C).

Pressure Hysteresis: 

±0.1% FS.

Pressure Limits: 

See chart

Temperature Limits:

Operating: 0 to 140°F (-17.8 to 60°C); Process with -HKIT

option: -20 to 180°F (-29 to 82°C); Storage: -4 to 176°F (-20 to 80°C).

Display: 

4-digit LCD (.425˝ H x .234˝ W digits).

Resolution: 

See chart.

Process Connections:

Two 1/8˝ (3.18 mm) female NPT; -HKIT option: Two 1/4˝

male 45° flare fittings. 

Power Requirements:

9 V alkaline battery, installed non-functional, user

replaceable.

Weight:

14.1 oz (400 g); -HKIT option: 3.6 lb (1.63 kg).

Agency Approvals:

CE.

Series 490A Hydronic Differential Pressure Manometer

are versatile, hand-held,

battery  operated  manometers  available  in  several  basic  ranges  for  positive  or
positive  differential  pressure  measurement  and  can  tolerate  most  liquid  media
compatible with 316LSS. A memory function allows storage of up to 40 readings for
later recall and a backlight provides auxiliary lighting for hard-to-see locations.
Standard are a hold feature and both visual and audible overpressure alarms. A
new feature added to the Series 490A is a field adjustable damping, independent
viewable high/low pressure readings, and low range increased resolution. This
allows the user to choose the level of display averaging rate corresponding to the
fluctuation level common in many applications. A 9 V alkaline battery is included
that provides up to 100 hours of operation.

Model 
490A-1
490A-2
490A-3
490A-4
490A-5
490A-6

English
Range

0 to 15 psi
0 to 30 psi
0 to 50 psi
0 to 100 psi
0 to 500 psi
0 to 200 psi

Metric
Range

0 to 103.4 kPa
0 to 206.9 kPa
0 to 344.8 kPa
0 to 689.5 kPa
0 to 3448 kPa
0 to 1379 kPa

Maximum
Pressure

30 psi (2.7 bar)
60 psi (4.13 bar)
100 psi (6.89 bar)
200 psi (13.78 bar)
1000 psi (68.9 bar)
400 psi (27.57 bar)

Available Engineering Units

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

psi, in w.c., in Hg, cm w.c., mm Hg, kPa, hPa, mbar, bar, oz/in

2

6-15/64

[158.27]

29/32

[22.86]

2-53/64 [71.73]

1/8 NPT

1-1/4

[31.75]

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание 490A-1

Страница 1: ...age of up to 40 readings for later recall and a backlight provides auxiliary lighting for hard to see locations Standard are a hold feature and both visual and audible overpressure alarms A new feature added to the Series 490A is a field adjustable damping independent viewable high low pressure readings and low range increased resolution This allows the user to choose the level of display averagin...

Страница 2: ...ating range of the unit Exceeding the range will not damage it or affect calibration as long as the maximum rated pressure is not exceeded The maximum pressure for all units is shown on the rear label and on page 1 of these instructions Do not exceed the maximum rated pressure of the manometer Doing so will cause permanent damage to the sensor may rupture the housing and or cause personal injury C...

Страница 3: ...ease 2 Next press the UNITS LOC button to change the source to the one desired 3 Press the ZERO STORE or ON OFF or HOLD MEMORY button to store the source and resume pressure measurement To return to any other pressure source reading please return to step 1 Note The unit will default to DIFF when powered on to return to a differential pressure reading DIFF HIGH LOW simply turn the unit off and then...

Страница 4: ...s V2 and V3 open Then using the bleed fittings once more loosen and bleed out the pressurized fluid or gases The PVC tubing can be used once more to control the bleeding of the fluid into a container or reservoir 6 Maintaining the integral hose ball valves in the closed position disconnect from the pressure test ports Figure C Figure D 7 5 64 179 78 11 55 64 301 23 3 5 32 80 17 3 5 32 80 17 LOW PR...

Отзывы: