Duomo KS22 Скачать руководство пользователя страница 1

t: 

01905 797989

e: 

[email protected]

 | w: 

www.duomo.co.uk

1

KS22 

Trio Safestart for G621

FEATURES

 

Touchpad control panel suitable for use with G621

 

Gas Safestart Gas proving system.

 

Unique, programmable access code

 

Starts ventilation, checks fan operation, starts Gas

 

Visually displays failure type (Air or Gas)

 

Automatically isolates gas supply at low pressure

 

Checks downstream pipework before initiating gas 

supply.

 

IGE/UP/2 Edition 2 and BS6173:2009 compliant

 

2 year guarantee - 3 year by registering at duomo.co.uk

SPECIFICATION

Power

Power Supply

230VAC 50Hz/60Hz ± 15%

Power Consumption

7VA Maximum

Max out Current (All relays)

3A resistive

Max out Switching Voltage

250VAC / 100VAC

Max out breaking capacity

2500VA

Out contact operations

> 100 x 103

External limit contact

> 3A @250VAC

Line Fuse 5 x 20

SNOWBLOW 3A

Technical Specification

Dimensions

Width 200mm 

|

 Height 110mm 

|

 Depth 60mm

Display

N/A (Illuminated Touchpad)

Mounting

Wall mounted

Relative Humidity

Also condensing 90% max

Working Temperature

0 to 60°C

Storage Temperature

20 to 80°C

Protective Rating

IP66

Configuration

G621 Safestart Assembly max 

Operating Pressure

50mbar

Approvals, Certifications and Guarantee

Guarantee

2 year as standard 

3 year by registering at www.duomo.co.uk

Gas

Proving 

System

Touchpad

Control

G621

Compatible

Access

Code

Dimensions

Содержание KS22

Страница 1: ...pply 230VAC 50Hz 60Hz 15 Power Consumption 7VA Maximum Max out Current All relays 3A resistive Max out Switching Voltage 250VAC 100VAC Max out breaking capacity 2500VA Out contact operations 100 x 103 External limit contact 3A 250VAC Line Fuse 5 x 20 SNOWBLOW 3A Technical Specification Dimensions Width 200mm Height 110mm Depth 60mm Display N A Illuminated Touchpad Mounting Wall mounted Relative Hu...

Страница 2: ...the Trio Safestart to a power supply A self test procedure will run If a failure is detected the green POWER light will blink and local buzzer will sound 1 5 Hz 2 Enter numeric password 1 to 8 characters At each press the active key will turn to red and a short tone will confirm the operation Push the to confirm the code and run the proving test NOTE In case of incorrect password the buzzer will m...

Страница 3: ...uk 3 2 1 3 POWER AIR GAS E E Ph N GND 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Output Terminal Input Terminal Stop Key Gas Light Abort Key Enter Key Fuse 3A Power on Light Air Light 1 2 4 5 7 8 3 6 9 X 0 STOP KS22 Keypad Layout Terminal Connections ...

Страница 4: ...electrical connection schematic for a commercial catering kitchen Flame failure devices ARE NOT fitted to all gas appliances This system shows Ventilation proved using ADP10 air pressure switches Fig 2 A Typical electrical connection for a commercial catering kitchen when flame failure devices are fitted to all gas appliances This system shows ADP10 air pressure switches for supply and extract Fig...

Страница 5: ...ooting The Problem The Solution Blank display If no E stop fitted Link out E E Terminals Still experiencing difficulties If you have made the checks above and are still experiencing diffculties then please call Duomo UK Ltd on 441905 797989 for technical assistance ...

Страница 6: ...t 01905 797989 e sales duomo co uk w www duomo co uk 6 ...

Страница 7: ...t 01905 797989 e sales duomo co uk w www duomo co uk 7 Notes ...

Страница 8: ...hire WR9 9AH GAS SAFETY CONTROLS DuomoUK linkedin com company duomo uk KS22 Trio Safestart 11032021 rev2 This document is protected by copyright No changes by others are permitted without prior authorisation by Duomo UK Ltd Duomo UK Ltd reserve the right to modify and revise this datasheet without notification ...

Отзывы: