1

BX150 

1 Channel Panel Mounted Gas Detection Controller

FEATURES

 

Single channel protection

 

230VAC or 12VDC supply

 

Panel mounted only

 

Positive safety option

 

Internal audible alarm

 

Manual test function

 

Self-diagnostic

 

Detection of Toxic 0-300ppm / Explosive Gas(es) 

0-20%LEL 

 

4-20mA signal input

 

2 alarm stages - Pre-alarm and main alarm

 

Sensor fault relay output

 

IP42 protective rating

 

CE certified and approved to EN 61010-1, EN 50270, 

 

EN 50271, EN 45544-3, EN 60079-29-1

 

2 year guarantee - 3 year by registering at duomo.co.uk

OVERVIEW

The BX150 is a single channel, panel mounted gas detection 

controller. It can be connected to toxic and explosive sensors.

If the remote sensor senses the presence of gas, it sends a 

proportional  4-20mA  signal  back  to  the  BX150.  When  the  first 

alarm level is reached the pre-alarm relay is activated (See Alarm 

Settings). If the level continues to rise the main alarm relay will be 

energised.

For explosive or toxic gases, the electrical supply to the safety shut 

off  valve  is  broken  when  the  main  alarm  threshold  is  reached. A 

general alarm is sounded. 

Should the controller enter fault condition the safety shut off valve 

closes to failsafe. A self-diagnostic feature looks for return sensor 

voltage and ensures correct functionality.

The BX150 controller is compatible with all the Duomo conventional 

sensors shown on pages 6 & 7.

SPECIFICATION

Power

Power Supply

230VAC 50Hz ± 10%

Secondary Battery

12VDC ± 10% max 2.2Ah

Battery Charger

Charger capacity 2.2Ah

Power Consumption

12V - 2.5W maximum

230V - 9W maximum

Relay Contact Range

10A resistive

Alarm Settings

Pre-Alarm No.1

13% LEL / 200ppm 

Pre-Alarm No.2

N/A

Main Alarm

Fixed at 20% LEL / 300ppm

Sensor Fault

Short circuit, interruption, sensor deterioration

Technical Specification

Dimensions

Width 48mm 

|

 Height 96mm 

|

 Depth 119mm

Display

N/A

Mounting

Panel mounted

Input Signal

4-20mA

Device Precision

1% FS

Reaction Time

<2 seconds

Working Temperature

-10°C to 40°C

Start-up Self-Diagnostic Delay

120 seconds

Protective Rating

IP42

Configuration

Positive Safety

Yes (ON/OFF)

Main Alarm Relay Actuation

Yes (Latching/Temporary Alarm)

Gas Type Selection

Yes (Toxic/Explosive)

Timed Sensor Test Facility

No

Emergency Stop Connections

No

O

2

 Compatibility as Standard

No 

Perhipheral Specification

No. of Remote Sensors 

Maximum Sensor Distance

100m

Cable Diameter for Sensors

1mm

2

 CSA 

(Screened and earthed at the controller end)

Compatibility

Sensor Compatibility

All Duomo sensors

Approvals, Certifications and Guarantee

Approvals

EN 61010-1, EN 50270, EN 50271, EN 45544-3, 

EN 60079-29-1

Guarantee

2 year as standard 

3 year by registering at www.duomo.co.uk

Panel Mounted 

Only

4-20mA

IP42

Manual test

Self-diagnostic

1

Channel

Содержание BX150

Страница 1: ...s for return sensor voltage and ensures correct functionality The BX150 controller is compatible with all the Duomo conventional sensors shown on pages 6 7 SPECIFICATION Power Power Supply 230VAC 50Hz 10 Secondary Battery 12VDC 10 max 2 2Ah Battery Charger Charger capacity 2 2Ah Power Consumption 12V 2 5W maximum 230V 9W maximum Relay Contact Range 10A resistive Alarm Settings Pre Alarm No 1 13 LE...

Страница 2: ...o co uk w www duomo co uk 2 BX150 Reset Test Fault Gas Pre Alarm Alarm 300 200 120 ppm Power Battery 20 13 8 LEL CO Over Load Sensor Battery 3 2 4 5 6 1 ON 1 2 1 3 119 110 48 48 96 46 93 Cutout Dimensions mm Overall Dimensions mm ...

Страница 3: ...d resets detector after alarm or fault condition 7 BATTERY LED illuminates when BX150 is being powered by standby batteries LED flashes when battery has low charge 8 MAIN ALARM 20 L E L concentration of gas detected Main alarm relay actuated 9 TOXIC Illuminates when internal DIP switch for carbon monoxide is set to the carbon monoxide position 10 FAULT Indicates a fault condition short circuit sen...

Страница 4: ... carbon monoxide is to be sensed on a given zone move the switch to the OFF position If explosive e g natural gas LPG hydrogen etc move the switch to the ON position Example shows explosive gas setting Dip Switch 2 Main alarm relay actuation method This can be configured to provide either a latching or a temporary alarm operation When the main alarm is actuated in an alarm condition if the switch ...

Страница 5: ...rrent regulations The plug in terminal rail makes installation easy and quick Do not mount close to any heat source or in an area where moisture is likely to effect operation The IP rating of this unit is IP42 Sensors should be positioned as shown below If you require any guidance on this please call Duomo technical support on 44 1905 797989 Important Notes Always check the wiring before powering ...

Страница 6: ...ovals EN 50270 EN 50271 EN 45544 1 3 Compliant Technical Specification Gas es Detected Carbon Monoxide Dimensions Width 100mm Height 100mm Depth 60mm Display N A Sensor Technology Electrochemical Settings Preset to TWA Alarm 1 and 2 STEL Standards Alarm 3 Output Signal 4 20mA Sensor Range 0 300ppm Working Temperature 20 C to 50 C Autosetting Yes Protective Rating IP66 Enclosure IP65 Sintered Head ...

Страница 7: ...30 Enclosure Approvals EN 50270 EN 50271 EN 60079 29 1 4 20mA 4 20mA IP64 IP30 LPG Natural Gas O2 HCF100 Refrigerant Gas Sensor SGM595 Natural Gas or LPG Sensor Technical Specification Gas es Detected Freons Inc R134A R404A R407C R410A Dimensions Width 76mm Height 150mm Depth 58mm Display N A Sensor Technology Semiconductor Settings N A Output Signal 4 20mA Sensor Range 0 300ppm Working Temperatur...

Страница 8: ... will be actuated In addition to keeping the pre alarm relay switch on the main alarm relay will be changed over The alarm LED will light to show that the system is in alarm and the buzzer will issue a higher frequency sound By releasing the the manual TEST button the LED s will go out and the audible alarm will cease If a latched alarm function on the main relay is configured this will remain on ...

Страница 9: ...heck the sensor The BX150 is issuing an alarm and does not shut off the devices connected to it Check that the wiring is correct and that the DIP switch has been set properly All relays must be free from electrical powe Check the drawing of the connections A 12V solenoid valve which does not work well is connected to the BX150 Direct connection of 12V solenoid valves or sirensto the BX150 is not p...

Страница 10: ...essful A Duomo Commissioning Certificate is provided A certificate from the original maufacturer ensures that the commisioning or servicing carried out is at a high professional standard by a competent and qualified service engineer It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first to...

Страница 11: ...t 01905 797989 e sales duomo co uk w www duomo co uk 11 Notes ...

Страница 12: ...cestershire WR9 9AH GAS SAFETY CONTROLS DuomoUK linkedin com company duomo uk BX150 14082019 rev1 This document is protected by copyright No changes by others are permitted without prior authorisation by Duomo UK Ltd Duomo UK Ltd reserve the right to modify and revise this datasheet without notification ...