AL VENTING INSTRUCTION

CAST IRON PRESSURE-FIRED

WET BASE HOT WATER BOILERS

 P/N 240005665, Rev. 1.1 [05/06]

!  

!  

!  

!  

Tested For 100 LBS.

ASME

Working Pressure

C.S.A. Certified

For Natural Gas Or Propane

CAUTION

Do not use this vent pipe or fittings for vent-

ing incinerators of any kind.

        

WARNING

For correct installation of your venting sys-

tem, read all of these instructions and refer 

to the vent pipe manufacturer’s instructions.

Failure to use a proper venting system will 

void the manufacturer’s warranty and may 

result  in  rapid  deterioration  of  the  venting 

system, a potential health hazard. 

Faulty  vent  installation  can  allow  toxic 

fumes to be released into living areas. This 

may cause serious bodily injury or property 

damage. Vent performance may also be af-

fected by improper assembly.

Install  separate  vents  for    forced  exhaust 

appliances  and  natural  draft  appliances. 

A  common  vent  between  natural  draft  and 

forced exhaust appliances may cause toxic 

gases to exhaust through the natural draft 

appliance  rather  than  to  the  outside  air. 

Breathing exhaust gases will cause serious 

personal injury or death. 

WARNING

All installations of boilers and venting should 

be done ONLY by a qualifies  expert and in 

accordance with the  appropriate manual. In-

stalling or venting a boiler or any other gas 

appliance with improper methods or materi-

als may result in serious injury or death due 

to fire  or asphyxiation from poisonous gases 

such as carbon monoxide which is odorless 

and invisible.

Содержание DPFG Series

Страница 1: ...be released into living areas This may cause serious bodily injury or property damage Vent performance may also be af fected by improper assembly Install separate vents for forced exhaust appliances...

Страница 2: ......

Страница 3: ...ill usually be adequate to provide air for combustion The doors should not t tightly Do not caulk the cracks around the windows An uncon ned space is de ned as a space whose volume is not less than 50...

Страница 4: ...s Vents and Solid Fuel Burning Appliances These codes contain information on special gas vents for Category II III and IV appliances vent sizing location air space clearances to combustibles and safe...

Страница 5: ...venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other de ciencies which could cause an unsafe condition 3 Insofar as is prac...

Страница 6: ...ing and walls near ue pip with reproof insulation Where two or more appliances vent into a common ue the area of the common ue must be at least equal to the area of the largest ue plus 50 percent of t...

Страница 7: ...mber of elbows 6 Do not connect to replace ue 7 The end of ue pipe must be ush with the inside face of chimney ue 8 Support the ue pipe rigidly with substantial hangers plus three sheet metal screws a...

Страница 8: ...take piping A B Vent shall not be used in the vent system The exhaust terminal included in the FDVS kit is a model FDVS stainless steel vent hood Located on an exterior wall of the building the exhaus...

Страница 9: ...amaged by exhausted ue gas FIG 5 EXTERIOR EXHAUST TERMINAL LOCATIONS NOTES Location of the termination of the vent pipe shall be in accordance with the National Fuel Gas Code A N S I Z223 1 see requir...

Страница 10: ...room oor C When a vacuum relief is not used note that exhaust fans in use might create a vacuum within the building which can cause improper combustion Consult factory for assistance as required D Se...

Страница 11: ...Clay pipe must pitch downward away from foundation to per foot 3 Con guration of transition from tee to topper is dependent on the type of the topper selected and the level of the nished grade Topper...