Dungs DMV-D(LE) 704/6x4 Series Скачать руководство пользователя страница 1

1 … 9

MC • Karl Dungs

, Inc.

 • DMV

-D(LE) 704/6x4 • Edition 2017.05 • P/N 261430

CSA:

Certified File No.112901

Commonwealth of Massachusetts Approved Product Approval code G1-1107-35

DMV-D(LE) 704/6x4

Dual Modular NEMA 4x 

Safety Shutoff Valves with 

Proof of Closure

Installation Instructions

Table of Contents

USA

CDN

Table of Contents  . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Attention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Specification  . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2

Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3

Painting Valve  . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3

Protection from Radiant Heat . . . . . . . . . . . . . . Page 3

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4

Valve Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . Page 4

Side Taps  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5

Valve Leakage Test . . . . . . . . . . . . . . . . . . . . . . . Page 6

Proof of Closure. . . . . . . . . . . . . . . . . . . . . . . . . . Page 7

Flow Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8

Pressure Drop for other Gases . . . . . . . . . . . . . Page 8

Pulse Fired Applications  . . . . . . . . . . . . . . . . . . Page 9

Approvals

1, 2, 3 ... 

= Action 

= Instruction

Explanation of symbols

On  completion  of  work  on  the 

safety valve, perform a leakage 

and function test.

Please read the instruction be-

fore installing or operating. Keep 

the instruction in a safe place. You 

find the instruction also at www.

dungs.com If these instructions 

are not heeded, the result may 

be personal injury or damage to 

property.

Any adjustment and application-

specific adjustment values must 

be made in accordance with the 

appliance-/boiler manufacturers 

instructions.

Attention

Check the ratings in the speci-

fications to make sure that they 

are suitable for your application.

This  product  is  intended  for 

installations  covered  by,  but 

not  limited  to,  the  following 

fuel gas codes  and standards: 

NFPA  54,  IFGC  (International 

Fuel Gas Code), or CSA B149.1 

(for  Canada)  or  the  following 

equipment codes and standards: 

CSD-1, NFPA 86, NFPA 37, ANSI 

Z83.4/CSA 3.7, ANSI Z83.18, ANSI 

Z21.13/CSA 4.9, or  CSA  B149.3 

(for Canada).

[

V

] [

A

]

[

Hz

]

 

[

VA

]

Safety

first

O.K.

IFGC

CSA

UL

ANSI

NFPA

Multiple Burner Applications. . . . . . . . . . . . . . . Page 9

Accessories & Replacement . . . . . . . . . . . . . . . Page 9

The installation and maintenance 

of  this  product  must  be  done 

under the supervision of an ex-

perienced and trained specialist. 

Never perform work if gas pres-

sure  or  power  is  applied,  or  in 

the presence of an open flame.

Содержание DMV-D(LE) 704/6x4 Series

Страница 1: ...ioninasafeplace You find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Any adjustment and application specific adju...

Страница 2: ...LE 704 90 VA DMV D 624 Two normally closed automatic shutoff valves in one housing Valve 2 V2 incorporates proof of closure V1 and V2 are fast opening fast closing Adjustable max flow with V2 Position...

Страница 3: ...nges 1 Unpack the DMV valve and remove the bolts by using 13 mm wrench 2 Remove the two protective covers 3 Verify the o rings and the grooves are clean and in good condition 4 Install the DMV valve w...

Страница 4: ...d screw until you can freely rotate the flow adjustment Turn clockwise for less gas or counterclockwise for more gas Check the flow at the burner with an orifice or flow meter 3 Tighten the pan head s...

Страница 5: ...5 9 MC Karl Dungs Inc DMV D LE 704 6x4 Edition 2017 05 P N 261430 Side Taps 1 2 3 4 5 7 5 4 3 2 1 V1 V2 pmax 7 PSI 4 5 3 2 1 3 2 1 1 2 3 4 5 7 5 4 3 2 1 V1 V2 p max 7 PSI 5 1...

Страница 6: ...e energize the burner system and verify that both automatic safety shutoff valves are closed 3 Close the upstream and downstream manual ball valve 4 Using a screwdriver slowly open the V1 test nipple...

Страница 7: ...terminal of the Flame Safeguard and N to L2 The ORANGE light shall be on when the valve is closed the GREEN light shall be on when the valve is open FM requirement Annual Testing All wiring must compl...

Страница 8: ...rrected flow rate in CFH through the valve for the other gas used For example when using propane divide the volume CFH of propane required for the application by the calculated value f f 0 66 for prop...

Страница 9: ...fired applications the fol lowing apply Before installing the valve the inside of all gas piping up stream to the nearest filter shall be cleaned and that filter shall have an insert with mesh no larg...