Service Manual for
RCO Speed Oven
48
#
NAME
DESCRIPTION
SETTING DEF SETTING/RANGE
o3-01 Copy Function
Selection
Changes some parameter default
settings depending on the region.
This parameter controls the
copying of parameters to and from
the LED operator (option).
Note:
When using the copy function, the
drive model number (o2-04) and
the software number (U1-14) must
match or an error will occur.
0
0
0: COPY SELECT (no function)
1: INV ==> OP READ –
All parameters are copied from
the drive to the LED operator
2: OP ==> INV WRITE –
All parameters are copied from
the LED operator to the drive
3: OP <==> INV VERIFY –
Parameter settings in the drive
are compared to those in the LED
operator
vA: Inverter capacity display
Sno: Software No. display
o3-02 Copy Allowed
Selection
Enables and disables the digital
operator copy functions.
0
0
0: Disabled – No digital operator
copy functions are allowed
1: Enabled – Copying allowed
o4-01
Accumulated
Operation Time
Setting
Sets the value for the cumulative
operation time of the drive.
0
0 to 9999 (10 hour units)
o4-02
Accumulated
Operation Time
Selection
Determines how the cumulative
operation time (U4-01) is counted.
0
0: Logs power-on time.
1: Logs operation time when
the drive output is active (output
operation time).
o4-03
Cooling Fan
Operation Time
Setting
Sets the value of the fan operation
time monitor U4-03.
0
0 to 9999 (10 hour units)
o4-05
Capacitor
Maintenance
Setting
Sets the value of the capacitor
maintenance time monitor U4-05.
0
0 to 150%
o4-07
Soft Charge
Bypass Relay
Maintenance
Setting
Sets the value of the Soft Charge
Bypass Relay Maintenance monitor
U4-06.
0
0 to 150%
o4-09
IGBT
Maintenance
Setting
Sets the value of the IGBT
Maintenance monitor U4-07.
0
0 to 150%
o4-11
U2 initialize
Selection
Selects if U2-XX (Fault Trace)
monitors are reset at drive
initialization.
0
0: Saves the fault monitor data
1: Resets the fault monitor data