Service Manual for
RCO Speed Oven
44
#
NAME
DESCRIPTION
SETTING DEF SETTING/RANGE
H3-01
Terminal A1
Signal Level
Selection
Sets the input level for terminal A1.
0
0
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
H3-03 Terminal A1 Gain
Setting
Sets the level of the input value
when 10 V is input at terminal A1.
100.0
100.0 -999.9 to 999.9%
H3-04 Terminal A1 Bias
Setting
Sets the level of the input value
when 0 V is input at terminal A1.
0.0
0.0
-999.9 to 999.9%
H3-13 Analog Input Filter
Time Constant
Sets the primary delay filter
time constant for terminal A1 or
potentiometer (optional). Used for
noise filtering.
0.10
0.03 0.00 s to 2.00 s
H4-01
Multi-Function
Analog Output
Terminal AM
Selects the data to be output
through the multi-function analog
output terminal AM>
102
102 000 to 999
H4-02
Multi-Function
Analog Output
Terminal AM Gain
Sets terminal AM output level when
selected monitor is at 100%.
100.0
100.0 -999.9 to 999.9%
H4-03
Multi-Function
Analog Output
Terminal AM Bias
Sets terminal AM output level when
selected monitor is at 0%.
0.0
0.0
-999.9 to 999.9%
H5-01 Drive Slave
Address
Selects drive slave number
(address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle
power for the setting to take effect.
0001F
001F 0 to 32
H5-02 Comm. Speed
Selection
Selects the baud rate for
MEMOBUS/Modbus terminals R+,
R-, S+ and S-. Cycle power for the
setting to take effect.
3
3
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
H5-03 Comm. Parity
Selection
Selects the communications parity
for MEMOBUS/Modbus terminals
R+, R-, S+ and S-. Cycle power for
the setting to take effect.
0
0
0: No parity
1: Even parity
2: Odd parity
H5-04 Stopping Method
After Comm. Error
Selects the stopping method when
a communication time-out fault
(CE) is detected.
3
3
0: Ramp to stop
1: Coast to stop
2: Fast stop
3: Alarm only
H5-05
Comm. Fault
Detection
Selection
Enables or disables the
communications timeout fault (CE).
1
1
0: Disabled - A communication loss
will not cause a communication
fault.
1: Enabled - If communication is lost
for more than 2 seconds, a CE
fault will occur.
H5-06 Drive Transmit
Wait Time
Sets the wait time between
receiving and sending data.
10
10
10 to 65 ms
H5-07 RTS Control
Selection
Selects “request to send” (RTS)
control.
1
1
0: Disabled - RTS is always on
1: Enabled - RTS turns on only
when sending
H5-12 Run Command
Method Selection
0
0
0: FWD/STOP, REV/STOP method
1: RUN/STOP, FWD/REV method
H5-13
MEMOBUS
Frequency
Reference and
Frequency
Monitor Unit
0
0
0: 0.1 Hz / 1
1: o1-03 based
2: 100% / 30000
3: 0.1% / 1