background image

PACKAGE
STANDBY
SYSTEMS

INSTALLATION AND

OPERATIONS MANUAL

PSS30/A
(2009 to 2010)
Four Door Version

Содержание WINCO PSS30/A

Страница 1: ...PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS30 A 2009 to 2010 Four Door Version...

Страница 2: ...ned SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions...

Страница 3: ...electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or...

Страница 4: ...on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The 30 000 watt 30kW generator i...

Страница 5: ...temperature battery voltage speed engine load coolant level from ECU ECU specific parameters and run time statistics A Liquid Crystal Display The backlit 64 by 128 pixel LCD serves as the local infor...

Страница 6: ...setting or resetting the system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to e...

Страница 7: ...uld the instructions or information provided be interpreted to conflict with any local state or national codes If in doubt always consult your local fire marshal or gas supplier WARNING FIRE HAZARD Al...

Страница 8: ...led from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible obst...

Страница 9: ...performed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper...

Страница 10: ...Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition CONNECTING THE BATTERY CHARGER BLOCKHEATER A two...

Страница 11: ...ovided for you to connect your ground wire from the transfer switch to The lugs on the 40 kW will handle wire sizes 6 AWG to 250 MCM and should be torqued to 250 in lbs The lugs on the 30 kW will acco...

Страница 12: ...Once the relay is opened the unit will shut down and remain in the standby mode until the remote start relay is closed again F ESTOP ESTOP Remote Emergency Stop terminals These two terminals are shipp...

Страница 13: ...ator the next step is to check the voltage at the generator terminals in the Automatic Transfer Switch The voltage between the G1 and the G3 terminals should be the same as it was on the generator fro...

Страница 14: ...C generator output from generator 2 Defective transfer switch controller 3 Incorrect voltage or frequecy for the generator 4 Wiring error between generator and transfer switch 5 Defective mechinally s...

Страница 15: ...60706 190 Page 13 9158 00 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE...

Страница 16: ...Page 14 9158 00 60706 190 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS...

Страница 17: ...60706 190 Page 15 9158 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS...

Страница 18: ...Page 16 9158 00 60706 190 DC SCHEMATIC...

Страница 19: ...60706 190 Page 17 9158 00 PSS30LS OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES...