DTI WINCO PSS15B2W/A Скачать руководство пользователя страница 10

PAGE 8

60706-169

4190-00

         *************
*****  WARNING  *****
         *************
A service disconnect must be installed in front of the
A.T.S. panel as the A.T.S is not service entrance rated.
This will allow you to test the generator under load.
Should you ever have to work on the switch, you will be
able to disconnect the power and work on the switch cold
without having the power company pull your meter.

To wire the automatic transfer switch into the existing

wiring, first determine which circuits will be on the
emergency load circuit.  If the entire load is to be trans-
ferred, the transfer switch can be wired in directly after the
watt-hour meter and the service entrance, providing the
service entrance ampere rating is within the transfer
switch’s rated capability.

If only specific circuits are to be powered under emer-

gency power failure conditions, an additional distribution
panel designated “emergency distribution panel” must be
installed.

All selected emergency circuits are removed from main

distribution panels and reinstalled in the emergency
distribution panel.  Suggested circuits: freezer, refrigera-
tor, furnace, emergency lights, sump pump, emergency
outlet circuits, etc.  Total running load must not exceed
generator rating.

D.C. ELECTRICAL INTERCONNECTION

*******CAUTION******

Never run the AC and DC wiring in the same conduit.

WINCO NON-UL ATS

Two control wires are required to be installed between

the A.T.S. panel and the generator control terminal box.
Depending on the distance 14 to 16 gauge stranded wire
should be used.  These wires will be labeled  “Bat -”, and
“Start”.

The control wires will be connected as follows in the

generator control terminal box:

ATS Panel

Generator Control Panel

Start 1

 to

Wire # S1,  (Bat Neg)

Start 23

 to

Wire # S23 (Start)

ASCO 165 UL SWITCH

Your DC connection points in the ASCO 165 UL ATS

are on the terminal block in the upper right hand corner of
the ATS panel.  The terminal block is numbered 1 through
9.  You will be using terminals 4 and 5, wire Start 23 will
connect to terminal #5 and wire Start 1 will connect to
terminal #4.  See page 13 for a connection diagram.

ASCO 300 UL SWITCH

Your DC connection points in the ASCO UL ATS are

terminals “14” and “15” .Depending on the size of the
switch they are located in differnt locations.  See below

INITIAL START UP

         *************
*****  WARNING  *****
         *************
DO NOT jump start these engine generator  sets. Starting
these units on a low battery or jump starting them will
cause damage to the engine control module.

Use the following check list to verify correct installa-

tion before starting the engine:

F

Engine oil.*  Check level & fill as required with

proper grade/qty.

F

Unit mounting base properly bolted down.

F

Clearance for service and maintenance on all

sides.

F

Proper fuel line material, and size.

F

All fuel line connections tight.

F

Fuel line protected and a moisture trap installed
(may be required for N.G.).

F

LP/NG pressure O.K. 4-6 Oz. (7-11" WC).

F

Battery connections clean and tight.

F

Battery fully charged.

F

All A.C. and D.C. wiring installed and properly

protected.

* Refer to engine owners manual for proper
levels and type.

After completing the above checklist, the engine-

generator set is ready for the initial start-up test.

Содержание WINCO PSS15B2W/A

Страница 1: ...PACKAGED STANDBY SYSTEM PSS15B2W A INSTALLATION AND OPERATORS MANUAL Engine Generator Set...

Страница 2: ...rication 6 Battery Installation 6 Connecting Battery Charger 6 TRANSFER SWITCH INSTALLATION 6 AC Electrical Connections 7 DC Electrical Connections 8 INITIAL START UP 8 TROUBLESHOOTING INFORMATION 9 W...

Страница 3: ...ut of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropri...

Страница 4: ...UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100AMPS 60 AMPS UL Automatic Transfer Switch Sizes UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100 AMPS 100 AMPS 200 AMPS...

Страница 5: ...rrier for claim procedures Be sure to retain the packaging material for carrier inspection Concealed Damage is understood to mean damage to the contents of a package which is not evident at the time o...

Страница 6: ...stays clean WARNING FIRE HAZARD DO NOT OVERTIGHTEN THE FUEL LINE THIS IS A TAPERED FITTING OVERTIGHTENING WILL CAUSE THE FITTING TO CRACK AND LEAK FUEL For all vapor fuel systems the delivery pressure...

Страница 7: ...n inches of water column The second is with a pressure gauge calibrated in ounces per square inch Reference numbers 1 through 3 in the block diagrams above are system parts supplied by customer Refere...

Страница 8: ...battery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure...

Страница 9: ...ion panel should contain your only neutral to ground bond All power leads from the generator to the A T S must be sized to handle rated generator output amperage at a minimum the type of wire you use...

Страница 10: ...anded wire should be used These wires will be labeled Bat and Start The control wires will be connected as follows in the generator control terminal box ATS Panel Generator Control Panel Start 1 to Wi...

Страница 11: ...s you will have to fail the incoming line power to the A T S panel All the loads connected to the A T S should now be dead The engine generator set will go into a 3 to 10 second start delay At the end...

Страница 12: ...be 3600 RPM 9 AC short on output leads PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and the Automatic Tra...

Страница 13: ...PAGE 11 4190 00 60706 169 AC AND DC GENERATOR WIRING DIAGRAM...

Страница 14: ...PAGE 12 60706 169 4190 00 AC AND DC GENERATOR SCHEMATIC...

Страница 15: ...PAGE 13 4190 00 60706 169 GENERATOR LAYOUT...

Страница 16: ...ility and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation o...

Отзывы: