DSE DSE9701 Скачать руководство пользователя страница 1

 

 

D E E P   S E A   E L E C T R O N I C S  
 
D S E 9 7 0 1   &   D S E 9 7 0 2   B A T T E R Y   C H A R G E R  
I N S T A L L A T I O N   I N S T R U C T I O N S

 

053-170 

ISSUE 1

 

 

 DANGER OF DEATH

 : 

LIVE PARTS exist within the Battery Charger 

enclosure.  The enclosure cover must not be removed.

 

 

Installation 

The DSE9701 (24V 5A) & DSE9702 (12V 5A) battery chargers are designed to be mounted 
vertically within a control panel, on the panel DIN rail utilising the integral mounts or on a chassis 
utilising the mounting holes. For dimension and mounting details, see overleaf.  
DSE battery chargers are 

fit-and-forget.

 They are permanently connected to the supply and the 

load, with no requirement to disable the charger during times of heavy load (such as engine 
cranking) or when in parallel with a charging alternator. 

 

Battery Suitability 

The charger is factory set by DSE to suit Lead Acid batteries but can be adjusted at the time of 
ordering to suit other battery types.  
Care must be taken to ensure the batteries connected to the charger are of the correct 
‘technology’ to suit the setting of the charger. 

 

Indications 

The Battery Chargers feature an LED indicator(s) to show the battery charger 

Status.

 

(Refer to DSE publication:  057-085   DSE9xxx Series Operator Manual for further information)

 

 

Boost Mode

  

Boost mode is operated by connecting the 

BOOST

 terminals together for instance with an 

external switch or timer circuit. This will raise the battery charger floating voltage by 0.8V DC.  
 

Typical Wiring Diagram 

 

 

 

NOTE : This document is intended as a ‘quick start’ guide only. For full 

operating instructions and specifications, refer to DSE publication:  057-085   
DSE9xxx Series Operator Manual. 

Connection Type 

Screw Terminal, 
Rising Clamp,  
No Internal Spring 

Min Cable Size 

0.5mm² (AW G 20) 

Max Cable Size 

2.5mm² (AW G 14) 

DSE9701 AC Fuse  
(230 V AC Supply) 

2.0 A Anti-Surge

 

DSE9701 AC Fuse  
(110 V AC Supply) 

3.5 A Anti-Surge 

DSE9702 AC Fuse   
(230 V AC Supply) 

1.0 A Anti-Surge 

DSE9702 AC Fuse  
(110 V AC Supply) 

2.0 A Anti-Surge 

 