DSE DSE9474 Скачать руководство пользователя страница 1

 

 

ISSUE: 2 

 

 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

DEEP SEA ELECTRONICS PLC 

DSE9474 & DSE9484 OPERATOR MANUAL 

 

Document Number: 057-231 

 

Author: A.D.Manton 

 
 

Содержание DSE9474

Страница 1: ...ISSUE 2 DEEP SEA ELECTRONICS PLC DSE9474 DSE9484 OPERATOR MANUAL Document Number 057 231 Author A D Manton...

Страница 2: ...ance with the provisions of the Copyright Designs and Patents Act 1988 Applications for the copyright holder s written permission to reproduce any part of this publication must be addressed to Deep Se...

Страница 3: ...85 14 2 6 3 CAN 16 3 INSTALLATION 17 3 1 BATTERY SUITABILITY 17 3 2 USER CONNECTIONS 18 3 2 1 AC SUPPLY CONNECTIONS 18 3 2 2 INPUT OUTPUT AND RS485 CONNECTIONS 18 3 2 3 CANBUS AND TEMP SENSOR CONNECTI...

Страница 4: ...DSE website at www deepseaplc com The DSE9474 DSE9484 battery chargers are intended for mounting within a customer enclosure or panel fastened by screws bolts The DSE9474 DSE9484 include protected ou...

Страница 5: ...8 Hz 64 Hz Output Ripple and Noise 1 Vo Load Regulation 1 Vo Line Regulation 0 01 Vo Output Voltage Overshoot 5 Vo Transient Response Peak Deviation mV at 50 to 100 load step 4 Vo Warm Up Voltage V 1...

Страница 6: ...30 V Vo 29 5 V Io 30 A DSE9474 Full load AC input current A 9 A At Vin 110 V Vo 29 5 V Io 30 A DSE9484 Full load AC input current A 2 1 A At Vin 230 V Vo 14 75 V Io 30 A DSE9484 Full load AC input cur...

Страница 7: ...to Voltage compensation curves are used for the pre set battery types For custom battery types the temperature compensation curve is user configurable NOTE In the below chart VRLA Gel Lead Acid Antimo...

Страница 8: ...BETWEEN 110 V AND 305 V Example For AC voltage of between 110 V and 305 V if the ambient termperature is 73 C the charger is limited to 40 of it s configured current rating 2 3 3 2 TEMPERATURE DERATIN...

Страница 9: ...f the DSE947 DSE9484 2 3 4 1 INPUT POWER TO OUTPUT POWER EFFICIENCY DSE9474 2 3 4 2 INPUT POWER TO OUTPUT POWER EFFICIENCY DSE9484 Example With an input voltage of 240 V AC more than 93 5 of the input...

Страница 10: ...ounted with the base to a vertical surface with the terminal strips running horizontally Parameter Comment Weight 2 5 kg Case Dimensions 240 mm x 269 mm x 89 mm 9 4 x 10 4 x 3 5 Mounting Holes Dimensi...

Страница 11: ...cts with a diameter of more than 12 mm Fingers or similar objects prevented from approach No protection against water NEMA rating Enclosure type 1 Provides a degree of protection against contact with...

Страница 12: ...ation Specification USB Port USB 2 0 Device for connection to PC running DSE Configuration Suite Max distance 6 m 20 feet RS485 Serial Port Isolated Data Connection 2 Wire common Half Duplex Max Baud...

Страница 13: ...s are required DSE9474 24 V 30 A Battery Charger DSE9484 12 V 30 A Battery Charger DSE Configuration Suite Software Supplied on configuration suite software CD or available from www deepseaplc com USB...

Страница 14: ...2 2 MODBUS RTU RS485 is used for point to point cable connection of more than one device maximum 32 devices and allows for connection to PCs PLCs and Building Management Systems to name just a few de...

Страница 15: ...rue set to enabled Brainboxes VX 023 ExpressCard 1 Port RS422 485 for laptops and nettop PCs Brainboxes UC320 PCI Velocity RS485 card for desktop PCs Set to Half Duplex Autogating with CTS True set to...

Страница 16: ...ttery Charger 1 Output Voltage 4992 64789 20 0 1 s Battery Charger 1 Output Current 4993 64789 20 1600 1 s Net Battery Current 114 65271 1 125 1 s Battery Potential 168 65271 20 0 1 s Battery 1 Temper...

Страница 17: ...n this document The battery charger is fit and forget It can be permanently connected to the supply and the load with no requirement to disable the charger during times of heavy load such as engine cr...

Страница 18: ...RS485 CONNECTIONS Terminal Function Recommended Size Comments REMOTE SENSE Remote Sensing Wire negative terminal 1 mm AWG 16 Low current Sensing Wires used to measure the voltage at the battery termi...

Страница 19: ...AWG 22 CANBUS H CAN H Terminal 0 5 mm AWG 22 PT1000 TEMP SENSOR PT1000 Sensor As fitted to the PT1000 Sensor Battery Temperature Sensing Used for Battery Temperature Compensation PT1000 TEMP SENSOR PT...

Страница 20: ...Specifications 057 231 ISSUE 2 Page 20 of 30 3 3 TYPICAL WIRING DIAGRAM...

Страница 21: ...TS exist within the DSE9474 DSE9484 enclosures The enclosure cover must not be removed when connected to an AC supply Three LEDs are provided to show operating status and fault conditions These are de...

Страница 22: ...age Charge in Progress Green Flashing 4 2 FAULT CONDITIONS Condition LED Designation FAULT 1 FAULT 2 DC Over Volts Warning and Trip DC Under Volts Warning Battery Detection Warning DC Over Current Bat...

Страница 23: ...g conditions the Fault Relay de energises and charging is stopped DC output is disabled Mains voltage 310 V rms Mains voltage 85 V rms Battery temperature 60 C if temperature compensation is enabled B...

Страница 24: ...he Factory Setting for the digital input provides a Lamp Test function 5 3 PSU MODE NOTE For further details of PC Configuration refer to DSE Publication 057 159 DSE94xx Configuration Suite PC Softwar...

Страница 25: ...ant level boost voltage to allow the battery to charge while the load does not exceed the maximum rating of the charger If the load on the battery charger battery charge demand standing load exceeds t...

Страница 26: ...ttery Chargers will continue to recharge the battery until it is fully charged Typically a battery will charge from flat to 80 capacity in 16 hrs when charged at C 10 For example charging a 50 Ah batt...

Страница 27: ...operated Check the connected load of the charger is not reverse connected or short circuit Check the LED indications against the LED descriptions listed elsewhere in this document Batteries fail to c...

Страница 28: ...user serviceable part listed below In the case of malfunction contact your original equipment supplier OEM Description DSE Part Number Internal AC Fuse 15A 011 106 8 WARRANTY DSE provides limited war...

Страница 29: ...This Page is Intentionally Blank...

Страница 30: ...This Page is Intentionally Blank...