15

the Bell Cutoff time expires (Section [005] “System Times”), or
until a code is entered (see Section 5.13 

“Bell” on page 22).

NOTE: If a second Fire type zone is violated or if the Fire keys
are pressed during the delay period, the panel will latch the
alarm output and will immediately communicate the alarm.

A violated Fire zone will be displayed on all keypads and can
be delayed at any keypad. Typically this zone is used for
latching smoke detectors.

[08]  Standard 24 Hour Fire Zone

NOTE: Do not wire Fire zones on keypad zone terminals if the
DEOL supervision option is enabled for the panel (section
[013], option [2]).

When this zone is violated, the panel will immediately latch the
alarm output and communicate to the central station. The
alarm will sound until the Bell Cutoff time expires, or until a
code is entered (see section 5.13 

“Bell” on page 22).

A violated Fire zone will be displayed on all keypads. Typically
this zone is used for pull stations.

[09]  24 Hour Supervisory Zone

If this zone is violated when the system is either armed or dis-
armed, the panel will report to the central station, and will log
the zone alarm to the Event Buffer. This zone gives a silent
alarm by default.

NOTE: Do not wire 24-Hour Supervisory zones on keypad
zone terminals.

[10]  24 Hour Supervisory Buzzer Zone

If this zone is violated when the system is either armed or dis-
armed, the panel will immediately latch the keypad buzzer
until a valid access code is entered and will immediately com-
municate to the central station.

[11]  24 Hour Burglary Zone

If this zone is violated when the system is either armed or dis-
armed, the panel will immediately latch the alarm output and
communicate to the central station. The alarm will sound until
the Bell Cutoff time expires, or until a code is entered (see
section 5.13 

“Bell” on page 22).

[12] - [20]  

The following zone definitions operate similar to the 24 Hour
Burglary except for the System Event output type and the SIA
identifier:

[12]  24 Hour Holdup Zone

 - This zone gives a silent alarm by

default. 

[13]  24 Hour Gas Zone 
[14]  24 Hour Heat Zone 
[15]  24 Hour Medical Zone 
[16]  24 Hour Panic Zone
[17]  24 Hour Non-Medical Emergency Zone
[18]  24 Hour Sprinkler Zone
[19]  24 Hour Water Flow Zone
[20]  24 Hour Freezer Zone

[21]  24 Hour Latching Tamper

If this zone is violated, the installer must enter Installer’s Pro-
gramming before the system can be armed.

NOTE: Wireless zones should not be programmed as zone
types [22] - [24].

[22]  Momentary Keyswitch Arm Zone

Momentary violation of this zone will alternately arm/disarm
the system. Tampers and faults will not arm/disarm the sys-
tem, but only activate the appropriate trouble.

[23]  Maintained Keyswitch Arm Zone

When this zone is violated, the system will arm. When this
zone is secured, the system will disarm. Tampers and faults
will not arm/disarm the system, but only activate the appropri-
ate trouble.

[24] For future use

[25] Interior Delay Zone

This zone type is normally used with motion detectors and has
a standard exit delay time. 
If the panel is Away armed (a delay zone is violated during the
exit delay, or the Away function key is used), the Interior Delay
zone will work the same as the Interior zone [04].
If the panel is Stay armed (a delay zone is NOT violated dur-
ing the exit delay, the Stay key is used, or [*][9] is used for
arming), a violation of the zone will initiate Entry Delay 1.

[27] Push to Set Zone

If any zones are programmed as Push to Set, when the system
is armed, the panel will suppress all audible exit delay beeps/
squawks and begin an infinite silent exit delay. When a user
violates and restores a Push to Set zone, the panel will wait 5
seconds, then terminate the Exit Delay and arm the system.

NOTE: Do not enable Exit Delay Termination if this zone type
is used (see 5.18 

“Entry/Exit Delay Options”

 on page 24). Do

not change the attributes of Push to Set zones from the default
settings.

[28] 24 Hour Bell/Buzzer Zone

This zone works like a 24-Hour Burglary zone (zone type [11])
while armed, and a 24-Hour Supervisory Buzzer zone (zone
type [10]) while disarmed. When the panel is armed and this
zone is violated, the bell sounds until the bell time-out timer
expires. When the panel is disarmed and this zone is violated,
the keypad buzzers sound until a user enters an access code. 

[87]  Delayed 24 Hour Fire (Wireless)

This zone type operates the same as [07] Delayed 24 Hour
Fire Zone and must be used if the smoke detector is wireless.

[88]  Standard 24 Hour Fire (Wireless)

This zone type operates the same as [08] Standard 24 Hour
Fire Zone and must be used if the smoke detector is wireless.

Zone Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  [001]
Zone Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  [202]

5.3

Zone Attributes

NOTE: All zones, with the exception of 24 Hour and Fire, will
provide an exit delay. 

NOTE: Do not change the attributes for Fire Zones from the
default settings.

Additional zone attributes can be programmed to customize
the operation of a zone for a specific application. The follow-
ing attributes are programmable for each zone:

Audible / Silent –

 This attribute determines whether or

not the zone will activate the alarm output.

Pulsed / Steady –

 This attribute determines whether the

alarm output will be steady or will pulse on and off every
second.

Activate Chime –

 This attribute determines whether or

not the zone will activate the chime feature (see 

“[*][4]

Door Chime On/Off” on page 9).

Bypass Enable –

 This attribute determines whether or

not the zone can be manually bypassed (se

“[*][1]

Bypassing and Activating Stay/Away Zones” on page 7).

Содержание Power608

Страница 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Страница 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Страница 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Страница 4: ...ii PC5008 Wiring Diagram...

Страница 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Страница 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Страница 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Страница 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Страница 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Страница 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Страница 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Страница 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Страница 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Страница 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Страница 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Страница 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Страница 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Страница 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Страница 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Страница 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Страница 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Страница 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Страница 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Страница 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Страница 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Страница 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Страница 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Страница 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Страница 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Страница 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Страница 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Страница 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Страница 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Страница 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Страница 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Страница 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Страница 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Страница 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Страница 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Страница 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Страница 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Страница 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Страница 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Страница 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Страница 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Страница 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Страница 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Страница 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Страница 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Страница 50: ...46 NOTES...

Страница 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Страница 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Отзывы: