Section 5: Programming
184 – Open After Alarm
This output activates when the system has been disarmed after an alarm. It deactivates when a valid user code is entered or
when the PGM Output timer expires.
200 – Zone Follower - PGM By Zone
This option allows the PGM to activate when the assigned zone is opened and deactivate when the zone is restored or, if pro-
grammed, when a valid access code is entered. This PGM follows the state of the assigned zone, regardless of the partition
the zone or PGM is assigned to.
To program which zone the PGM will follow, see "[011] PGM Configuration Options" on page 85.
201-216 – Zone Follower (Zones 1-128)
This output type is assigned to a group of zones and is normally activated, but deactivates when a zone is tripped. Zones are
assigned to this output in the following groups:
201 –
Zones 1-8
209 –
Zones 65-72
202 –
Zones 9-16
210 –
Zones 73-80
203 –
Zones 17-24
211 –
Zones 81-88
204 –
Zones 25-32
212 –
Zones 89-96
205 –
Zones 33-40
213 –
Zones 97-104
206 –
Zones 41-48
214 –
Zones 105-112
207 –
Zones 49-56
215 –
Zones 113-120
208 –
Zones 57-64
216 –
Zones 121-128
If multiple zones are enabled, any active zone in that group triggers the output. The PGM will not activate again until all
zones are restored.
5.3.7 [010] PGM Attributes
The following options are used to program the operating characteristics of the main bell and PGM outputs.
[000] Main Bell Mask
This programming section is used to configure the types of audible alarms that trigger the main bell output on the alarm con-
troller. All options are selected by default.
Fire Alarm
ON: Fire alarm ([F] key, Fire zones) activates the main siren.
OFF: Fire alarm does not activate the main siren.
CO Alarm
ON: CO alarm activates the main siren.
OFF: CO alarm does not activate the main siren.
Burglary Alarm
ON: Burglary alarm (Delay, Instant, Interior, Stay/Away, Night, Interior Delay, Instant Stay/Away, Day, 24-hour Burglary)
activates the main siren.
OFF: Burglary alarm does not activate the main siren.
24-Hour Flood Alarm
ON: Main bell activates in the event of a 24-Hour Flood alarm.
OFF: Main bell does not activate in the event of a 24-Hour Flood alarm.
Bell Squawks
ON: Squawks activate the main siren. Bell squawks must be enabled to use the following options:
l
Bell Squawk on arm (single)
l
Bell Squawk on disarm (double)
l
Bell Duration Auto-Arm (single every second)
l
Bell Squawk on Exit (single every second)
l
Bell Squawk on Entry (single every second)
l
Bell Squawk on Trouble (single every 10 seconds)
- 77 -