
Section 5: Programming
[000] – Auto Enroll Modules
When this mode is selected, the alarm system automatically enrolls all modules connected to the Corbus. The total number
of modules currently enrolled are displayed on the keypad.
l
Enter sub-section [000] to begin auto enrollment of all new modules. The auto enroll screen will show the following:
l
KP = Number of keypad type modules
l
IO = Number of zone and output type modules
l
M = Number of other type modules
Devices are assigned to the next available slot. The slot assignment can be modified using subsections [002] and
[003].
[001] – Enroll Modules
To enroll modules individually:
1. Enter programming section [902][001].
2. When prompted, key in the serial number of the module found on the PCB. An error tone is sounded if an invalid serial
number is used.
3. To cancel enrollment of a module, press [#].
[002] – Module Slot Assignment (LED, LCD, ICON)
This section is used to change the slot number a module is enrolled in. To change the slot number:
1. Enter programming section [902][002].
2. Key in the serial number of the module.
3. When prompted, key in the new two-digit slot number. The previous slot assignment is replaced with the new one. An
error tone sounds if an invalid slot number is keyed in.
[003] – Edit Module Slot Assignment (LCD Keypad Only)
Like [002], this section is also used to change the slot number of a module. With this option, however, the serial number is
not required. To change the slot number:
1. Enter programming section [902][002].
2. Use the scroll keys to locate the module then press [*] to select.
3. Key in the new two-digit slot number. The previous slot assignment is replaced with the new one. An error tone sounds if
an invalid slot number is keyed in.
Deleting Modules
The following sections are used to remove modules from the system:
[101] – Keypads
[102] – 8-zone Expander Modules
[103] – 8-output Expander Modules
[106] – HSM2Host
[108] – HSM2955
[109] – Power Supply
[110] – 4 High Current Output
1. After entering section [902], scroll to the module type you want to delete (101-110).
2. Press [*] to select the module type then scroll to the specific module you want to delete.
3. Press [*] to select the module then, when prompted, press [*] again to delete.
[903] Confirm Module
The following sections are used to confirm enrollment of individual modules, their serial and slot numbers, and to locate
them physically:
[000] – View All Modules
[101] – Keypads
[102] – 8-zone Expander Modules
[103] – 8-output Expander Modules
- 118 -
Содержание Neo
Страница 6: ......
Страница 14: ...Section 2 Installation Figure 2 1 Wiring Routing North America only 14 ...
Страница 235: ......