Introduction

The FSA-410D is a 4-wire photoelectric smoke alarm with
optional: fixed temperature heat detector, auxiliary form C relay,
and/or remote LED output. 

Operation

Approximately every 7 to 8 seconds the unit tests for a smoke or
heat alarm condition. During this sequence the unit also performs
self diagnostics, and checks for faults. During normal operation
the LED will remain on to indicate energization of the unit and the
sounder will not sound.

Smoke Alarm

The smoke detector has a nominal fixed alarm sensitivity (refer to

Specifications

 on back page) and it will go into alarm when the

signal level exceeds the 'alarm' threshold. During an alarm the
LED will shut off, the sounder will sound continuous beeps and
the alarm relay will be activated. 

Remote Alarm - Interconnection

Multiple alarms can be connected using the PRM-4W Polarity
Reversal Module. When a fire alarm occurs, the unit will signal the

PRM-4W to reverse the polarity of the 4-wire loop. This will acti-
vate the sounders of all units connected on the loop. Refer to the
PRM-2W/4W Installation Manual for installation details.

Smoke - Drift Compensation

The unit automatically compensates for long-term environmen-
tally induced changes to maintain a constant smoke sensitivity.
When the drift compensation has reached its high or low limit of
adjustment, the unit will go into the trouble state.

Heat Alarm 

The heat detector will go into alarm when the heat signal level
exceeds the heat alarm threshold (135ºF/57ºC). During an alarm
the LED will shut off. The sounder will sound continuous beeps
and the alarm relay will be activated.

Alarm Restore

When the smoke clears from the unit and the heat signal falls
below the ‘restore’ level, the unit will automatically reset itself.

A = Activated / D = Deactivated

NOTE: 

For models FSA-410DFIS, the relay is deactivated, for all

other models the relay is activated during the condition.

Installer Instructions

1.  Smoke Alarm Placement

On smooth ceilings, units may be spaced 9.1m (30 ft) apart as a
guide. Other spacing may be required depending on ceiling
height, air movement, the presence of joists, uninsulated ceilings,
etc. Refer to CAN/ULC-S553-02 for installation recommendations. 

Do 

NOT

 locate smoke alarms at

the top of peaked or gabled ceil-
ings; the dead air space in these
locations may prevent the unit
from detecting smoke. Avoid areas
with turbulent air flow, such as
near doors, fans or windows.
Rapid air movement around the
detector may prevent smoke from
entering the unit.
Do 

NOT

 locate units in areas of

high humidity.

Do 

NOT

 locate units in areas where the temperature rises above

38ºC (100ºF) or falls below 5ºC (41ºF).

2. Mount Smoke Alarm Backplate

Mount backplate on standard 4” octag-
onal electrical box using the screws pro-
vided. 

NOTE:

 

Power must be supplied from a

ULC Listed power supply or alarm con-
trol unit auxiliary output. Install wiring
in accordance with the appropriate
national and local electrical codes.

CAUTION

: The dust cover protects the

unit when not in service. Remove the
dust cover before use.

FSA-410D Series Smoke Alarm

Installation and Operating Instructions

Read this instruction sheet thoroughly before installation and use of the FSA-410D Smoke Alarm

PA

IN

T

Piezo Sounder

Alignment Marks

LED/Test Button

DO

NO

T

Alarm Indications

Alarm Aux.

Condition

LED

Sounder

Relay

FormA

Relay 

FormC

Normal/Sensitivity in
Production Range

ON

OFF

D

D

Smoke Alarm

OFF

Steady

See Note

A

Heat Alarm

OFF

Steady

A

See Note

Alarm Restore

ON

OFF

D

D

Remote Alarm

ON

Steady

D

D

Low Power Trouble

ON

OFF

D

D

Other Fault / Trouble

ON

CHIRP 1/50s

D

D

Test Switch - Failed

ON

CHIRP 1/50s

D

D

Test Switch - Pass

OFF

Steady

A

A

Mounting Holes

Locking
Tab