Introduction

The FSA-210 is a 2-wire photoelectric smoke detector with
optional: fixed temperature heat detector, internal piezoelectric
alarm, auxiliary form C relay, and/or remote LED output. Three
version are available: US version (UL), Canadian version (ULC)
and an International version (EU).

Operation

Approximately every 7 to 8 seconds the unit tests for a smoke or
heat alarm condition. During this sequence the unit also per-
forms self diagnostics, and checks for faults. During normal
operation the LED will flash every 50 seconds and the sounder
will not sound.

Smoke Alarm

The smoke detector has a nominal fixed alarm sensitivity (refer
to the 

Specifications

 on the last page) and it will go into alarm

when the signal level exceeds the 'alarm' threshold and send
the alarm signal to the control panel. During an alarm the LED
will flash 1/second and the sounder will sound the the evacua-
tion temporal pattern (UL, EU) or continuous beeps (ULC). 

Remote Alarm - Interconnection

Multiple detectors (with sounders) can be connected using the
PRM-2W Polarity Reversal Module. When a fire alarm occurs,
the panel will signal the PRM-2W to reverse the polarity of the
2-wire loop. This will activate the sounders of all units con-
nected on the loop. Refer to the PRM-2W/4W Installation
Instructions for installation details.

Smoke - Drift Compensation

The detector automatically compensates for long-term environ-
mentally induced changes to maintain a constant smoke sensi-
tivity. When the drift compensation has reached its high or low
limit of adjustment, the detector will go into the trouble state.

Heat Alarm

The heat detector will go into alarm when the heat signal level
exceeds the heat alarm threshold (135ºF/57ºC); and send the
alarm signal to the control panel. During an alarm the LED will
flash 1/second and the sounder will sound the evacuation tem-
poral pattern (UL, EU) or continuous beeps (ULC).

Installer Instructions

1.  Smoke Detector Placement

On smooth ceilings, detectors may be spaced 9.1M (30 feet)
apart as a guide. Other spacing may be required depending on
ceiling height, air movement, the presence of joists, uninsulated
ceilings, etc. Consult National Fire Alarm Code NFPA 72, Chap-
ter 11 CAN/ULC-S553-02 or other appropriate national stan-
dards for installation recommendations. 

Do 

NOT

 locate smoke detectors at

the top of peaked or gabled ceilings;
the dead air space in these locations
may prevent the unit from detecting
smoke. Avoid areas with turbulent
air flow, (near doors, fans or win-
dows. Rapid air movement around
the detector may prevent smoke
from entering the unit. Do 

NOT

locate detectors in areas of high
humidity.

Do 

NOT

 locate detectors in areas where the temperature rises

above 38ºC (100ºF) or falls below 5ºC (41ºF).

FSA-210 Series Smoke Detector

Installation and Operating Instructions

Read this instruction sheet thoroughly before installation and use of the FSA-210 2-Wire Smoke Detector

PA

IN

T

Piezo Sounder

Alignment Marks

LED/Test Button

Place magnet here

DO

NO

T

Alarm Indications

Condition

LED

Sounder

Relay

Alarm

Current

Normal / Sensitivity 
in Production 
Range

Flash 1/50s

OFF

Deactivated

No

Alarm Smoke/Heat

Flash 1/1s

Temporal or

Steady

Activated

Yes

Alarm Restore

Flash 1/1s

Temporal or

Steady

Activated

Yes

Remote Alarm

Flash 1/50s

Temporal or 

Steady

Deactivated

No

Low Power Trouble

OFF

OFF

Deactivated

No

Other
Fault / Trouble

OFF

CHIRP 1/

50s

Deactivated

No

Test Switch - 
Failed

OFF

CHIRP 1/

50s

Deactivated

No

Test Switch - Pass

Flash 1/1s

Temporal or 

Steady

Activated

Yes