drive.web automation
smarty
Frequency Input Functions (FI Terminals)
FI
Digital and Event Inputs
- Maximum event frequency is
1/(2*FBE cycle s) Hz. For 5ms FBE cycle, the max event
frequency is 1/10ms = 100Hz.
FI
and
FT
thresholds with selectable, internal pull-up or pull-down.
Pull-Down = 2VDC (1.2Vmin, 2.9Vmax)
Pull-Up = 1.2VDC (0.5Vmin, 1.9Vmax)
FI Counter Inputs
- Provide frequency data with adjustable
moving-average filter and count outputs for use with
motion control function blocks.
FI Frequency Inputs
- Useful for lower frequencies
~<10kHz. Duty cycle is also measured. Updates every
FBE cycle or two-edge cycle.
smarty
XIO Digital IO Module Options
(Available Soon)
Up to eight modules may be added.
DINrail modules must be mounted directly to the right of the
smarty
carrier or the next
XIO
module in line.
Easy 4P4C plug-in, 60mm cable is included.
Module dimensions are the same as
C1
, page 6.
Separate manuals are supplied with each module.
XIO-8H-8H
- Eight 120VAC/240VAC inputs and eight
120VAC/240VAC outputs.
smarty
HG503894Iss2.0
Page /16
11