drive.web automation
dw230
Installation
Sample Rear View -
(
dw230-070
shown)
Power
: Regulated 22VDC min., 32VDC max., 6W. Do not
connect to a distributed DC power network. External 1A
fast-acting fuse or 1A current-limiting is required!
Connect to
+
and
-
on terminal block
P2
.
G
may be used
for earth or chassis ground connection.
Terminal wiring:
Strip 5mm(0.20”) or use ferrules.
0.2mm
2
(AWG24) min, 1.5mm
2
(AWG14) bare wire max.
Terminal tightening torque:
0.25 Nm (2.2 in
⋄
lbs) max.
Environment:
IP65 in front of supplied panel gasket.
IP20 inside panel environment, UL/IEC Pollution Degree
2, Humidity 95% max. non-condensing.
Temperature, Operating, 0°C to 50°C. Storage, -20°C to 60°C.
Altitude 3000m max.
Ethernet:
MDI 8P8C, “RJ45” jack, 100baseTX, 10BaseT, Full
Duplex, Auto-Negotiation, Auto-MDIX, IEEE 802.3ab.
100
Green LED indicates 100BaseTX Ethernet connection.
Link / Activity
Yellow LED. On for Link, flash for activity
USB:
Type A jack for USB pointer device, e.g. industrial mouse.
Plug device in prior to power-up.
dw230
Panel Mounting
Provide a cutout in a metal, industrial panel, 6mm (
¼
”) thick, max.
Ensure that the finished opening and surrounding area are flat,
1mm (0.04”) maximum deviation.
Install four panel-mounting clips and tighten screws, 0.25 Nm (2.2 in
⋄
lbs).
Do not over-tighten the clip screws! The screen may be
permanently damaged!
Model
W
idth
mm(inches)
H
eight
C
utout
w
idth
C
utout
h
eight
L
eft
Bezel
R
ight
Bezel
T
op
Bezel
B
ottom
Bezel
-50
150(5.9)
110(4.33) 140(5.51)
92(3.62)
5(0.2)
5(0.2)
10(0.39)
10(0.39)
-70
207(8.15) 139(5.47) 197(7.76) 118(4.65)
6(0.24)
5(0.2)
12(0.47)
9(0.35)
-97
252(9.92) 205(8.07)
229(9)
175(6.88)
12(0.47)
12(0.47)
16(0.63)
14(0.55)
savvyPanel touch
HG503545Iss2
www.driveweb.com
Page
"
/8
3
Panel Drawing Note:
Front view.
Grey bezel area must be
flat! See above.
Ch
Cw
Cutout
Dimensions
T
L
B
R
W
H
Panel-mounting clip
dw230
serial
number label
USB jack
Ethernet jack
Power;
+, -, G
.