background image

12

CRU

®

V TROUBLE-SHOOTING GUIDE (VAPOR-LOGIC

®

3

 only)

*Probe rod corrosion or probe head material aging may cause level control system failure. This generally does not occur in the first
two years of operation.

PROBLEM

POSSIBLE CAUSE

RECOMMENDED ACTION

Humidifier does not heat.

Incorrect or non-existent supply

voltage to unit

Check main line safety switch .
Check main line fuses.
Check for proper supply voltage.

Incorrect or non-existent control

voltage

Reset control transformer circuit breaker.

Check for 24 VAC control circuit voltage at T-1 and T-2 on the
control board.

Humidistat not calling

Set humidistat to call. Inspect for faulty humidistat.

Safety controls open.

Check safety controls, air flow switch,  and high limit humidistat.

Humidifier will not fill.

No water pressure at valve

Check water supply/shut off valves.

Faulty water fill valve

Check for 24 volts at the fill valve.

Plugged strainer

Check strainer.

Plugged valve

Check valve.

Faulty control board

Verify control voltage across the fill valve output.

Humidifier does not stop
filling.

Lack of tank to probes’ electrical
continuity; water conductivity 100
micromhos/cm (2 gr/gal) or 34.2
mg/1 min.

Add salt to the tank. If this solves the problem, consult factory for
further advice.

Fill valve stuck open

Check valve for foreign matter.

Drain valve not closed
Fill valve installed backward

Check for correct water flow, through valve, note arrow.

Auto-drain mode

Humidifier may be in periodic drain and flush. Check controller
display.

Low output

Electric drain valve not seating

Correct cause of leakage or replace valve.

Fill valve stuck open

Check valve for foreign matter.

Unit short cycles

Controller cycle rate set to low

Review controller cycle set point.

Reduced or no output even

though water is at the proper
level.

Heater malfunctioning

Verify that proper voltage is being applied to heaters. Check heater
amp draw and compare to wiring diagram ratings.

Malfunctioning control system

Heater contactor not functioning, replace. Service fuses blown.
Auxiliary limit controls not allowing system to operate (dust
humidistat, air flow proving switch, etc.) Reset, replace or calibrate
as required. Faulty or inaccurate humidistat, replace or calibrate.

Содержание CRUV

Страница 1: ...AND SAVE THESE INSTRUCTIONS DRI STEEM CRUV ELECTRIC STEAM HUMIDIFIER Installation Instructions and Maintenance Operations Manual For Toll Free Customer Support Call 1 800 328 4447 cETL LISTED ETL LIS...

Страница 2: ...ABLE OF CONTENTS TO THE PURCHASER AND THE INSTALLER Thank you for purchasing our CRU V humidification equipment We have designed and built this equipment to give you total satisfaction and many years...

Страница 3: ...gure 3 1 The CRU V Humidifier CRUV 6 25 shown CRUV 2 4 30 and 34 not shown Cover Heater terminal cover Steam outlet Over flow SST ball valve Water supply Cover bolts Float switch Heater element OM 770...

Страница 4: ...use a water seal and drain see examples in figures 4 2 and 5 1 The dispersion tube can also be placed vertically in the duct with some models see figure 5 2 Place the control cabinet or electrical sub...

Страница 5: ...n Tube Lower Than Humidifier OM 774 1 Tee 3 5 127 mm Water Seal When horizontally mounting the dispersion tube in an air stream that is located lower than the CRUV humidifier a water seal to prevent s...

Страница 6: ...1 40 9 600v 3 5 8 8 7 11 5 10 1 11 5 13 5 15 4 20 2 24 1 28 9 32 7 kW 2 0 4 0 6 0 8 0 10 0 12 0 14 16 0 21 0 25 0 30 0 34 0 CRU V Mechanical Electrical Specifications End Elevation OM 2002 Table7 2 C...

Страница 7: ...he drain and fill valves remain open for ten more minutes flushing the chamber 4 The drain valve then closes the chamber refills and the fill valve closes The timer resets and the unit resumesnormalop...

Страница 8: ...pair and push it on 2 Set the humidistat high enough so that unit will remain on call for at least one hour 3 After about 35 minutes of operation activation will take place causing the drain valve to...

Страница 9: ...tight 8 Reconnect drain line union fill valve supply line electrical connections to drain thermal trip heaters fill valve and probe Connect steam hose to top of tank 9 Verify drain valve lever is in...

Страница 10: ...ater conductivity 100 supply conductivity then consult factory micromhos cm 2 gr gal min Fill valve is stuck open Check valve for foreign matter Drain Valve not closed Check for correct water flow thr...

Страница 11: ...nt or cold state Excessive water pressure 100 psi maximum Obstruction will not allow float valve to seat properly clean or replace with new seat Verify that proper voltage is being applied to heaters...

Страница 12: ...l valve output Humidifier does not stop filling Lack of tank to probes electrical continuity water conductivity 100 micromhos cm 2 gr gal or 34 2 mg 1 min Add salt to the tank If this solves the probl...

Страница 13: ...l l i f k c e h C p o t s t o n s e o d r e i f i d i m u H g n i l l i f e v l a v n i a r d n e p O r o n a e l C e r u s o l c e t e l p m o c w o l l a t o n l l i w e v l a v n i a r d n i n o i...

Страница 14: ...e assy gasket 1 309750 003 8 probe assy CRUV 2 4 1 406270 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24v w flying leads 1 505084 12...

Страница 15: ...with conduit fitting 1 406050 100 7 probe assy gasket 1 309750 003 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24 v w flying leads 1...

Страница 16: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Страница 17: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Страница 18: ...n ordering Item Description Qty Part No 1 subpanel 13 X 15 1 165720 003 2 DIN rail 2 1 4 long 2 167765 0022 3 DIN rail 4 1 2 1 167765 0045 4 contactor 32A 1 407001 020 4 contactor 60A 1 407001 021 5 t...

Страница 19: ...19 MAINTENANCE SERVICE RECORD DATE INSPECTED PERSONNEL OBSERVATION ACTIONS PERFORMED...

Страница 20: ...DRI STEEM s limited warranty is made in lieu of and DRI STEEM disclaims all other warranties whether express or implied including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY ANY IMPLIE...

Отзывы: