Nozzle assembly in marathon
®
gas burners
dreizler A 3001 E - 18.12.2015 | A 2063 - 1.12 | EN - 09.11.2012
78
23.2 Nozzle assembly and flame-tube assembly gas-standard:
Gas part dual fuel burner for burn through combustion chamber
Fig. 23-2 Nozzle section
1
Set the outer nozzle bores outside of the flame conus
(standard approx. 1-2 mm, at M 10001.../M 10003... approx. 12 mm)
2
The flame tube conus must end flush with the front edge of the stabilising disk!
Tab. 23-1 Measurements burner type M...
NOTICE:
For more information see A 2054 chapter 24 "Nozzle bores in gas burners".
Burner type
Measure-
ments in mm
M...
A
601
35
1001/1501
35
2001/3001
40
5001
40
10001/10003
50