27
Faults, Cause and Remedy
403
Measured value of the Dräger-
Sensor XXS H
2
S is in the
negative range
Carry out the fresh air calibra-
tion, page 36.
404
DrägerSensor XXS H
2
S is not
inserted
Check DrägerSensor XXS H
2
S,
405
Error during the function test
with gas (bump test) of the
DrägerSensor XXS H
2
S
Repeat the function test, cali-
brate or replace the
DrägerSensor XXS H
2
S, if
necessary, page 46.
407
Failed filter test.
Repeat filter test with X-dock.
408
Failed rise time test.
Repeat rise time test with X-dock.
501
The zero point calibration of
the DrägerSensor XXS CO is
not valid
Carry out the fresh air calibra-
tion, page 36.
502
The span calibration of the
DrägerSensor XXS CO is not
valid
Carry out the span calibration,
503
The measured value of the
DrägerSensor XXS CO is in
the negative range
Carry out the fresh air calibra-
tion, page 36.
504
The DrägerSensor XXS CO is
not inserted
Check the DrägerSensor XXS
505
Error during the function test
with gas (bump test) of the
DrägerSensor XXS CO
Repeat the function test, cali-
brate or replace the DrägerSen-
sor XXS CO, if necessary,
507
Failed filter test.
Repeat filter test with X-dock.
508
Failed rise time test.
Repeat rise time test with X-dock.
Special symbol
»
«
and displayed numerical
code:
Cause
Remedy