44
Dräger VarioGard
Starting up the VarioGard system
8
Starting up the VarioGard system
During start-up, the VarioGard transmitter connected to the system
bus has to be calibrated with the target gas.
Connect the system to the power supply.
The system should be kept live until commissioning by Dräger Service.
The following settings and/or tests should be carried out to start the
installation:
Switch to menu operation and enter the password.
Set the language.
Set the clock.
Register all the slaves.
Test relays.
The factory default settings can only be changed by Dräger Service.
Have Dräger Service perform the commissioning.
8.1
Re-register all the slaves
This function is used to register all slaves with the central unit and give
them an address (necessary for starting up or upgrading the system).
The registration procedure can be repeated as often as desired and is
also required when permanently removing slaves from the system.
In measurement mode:
Press the
key.
NOTICE
After start-up the connected transmitters must be calibrated.
–
Display on central unit:
Dräger VarioGard
No transmitter !
Dräger VarioGard
## : ## Set clock !
–
The yellow LED flashes.
Mainten. necessary !
i
i
Enter password (for configuration).
Press the
key to change over to
menu mode. Display:
MENU:
MEASUREMENT
MODE
Using the keys
or
, select the
menu item
» REGISTER SLAVE «
.
MENU:
REGISTER SLAVE
Use the key
» y «
(yes) to register
slaves with the central unit.
Register slave ?
y / n
Press the
key. Display:
The central unit is now waiting for
registration of the individual slaves.
Register slave ?
0 Slave registered !
Press the
key (1) on the
transmitter for the different
slaves.
For the relay module and
converter module: follow the
installation instructions.
00733185.eps
V
arioGard
1
Содержание VarioGard
Страница 2: ......
Страница 179: ...Dr ger VarioGard 179 1 Dr ger Dr ger 195 2 i i...
Страница 182: ...182 Dr ger VarioGard 3 1 1 4 VarioControl 4 1 15 183 Dr ger VarioGard I 1 M 1 20 9 O2 I 2 18 ppm CO I...
Страница 184: ...184 Dr ger VarioGard A1 A2 A3 1 VarioGard ESC 00633185 eps 1 4 68 ppm NH3 I A1 i i 1 2 3 4 5 A1 A2 A3 A4...
Страница 185: ...Dr ger VarioGard 185 A1 A2 A3 A4 4 2 5 6 4 Escape Enter 5 1 i i ESC ESC...
Страница 187: ...Dr ger VarioGard 187 6 1 1 2 3 4 5 i i...
Страница 198: ...198 Dr ger VarioGard 9 3 9 4 VarioGard 3x00 2 VarioGard 3x00 2...
Страница 278: ......
Страница 279: ......