5.8
Settings instrument
5.8.1
Alarm settings
With factory default settings and during normal operation, the
relays are energized. This provides a “fail-safe” operation.
To switch the alarm On or Off:
1. Select
Settings > Instrument > Alarm > Alarm on/off
.
2. Select
Enable
or
Disable
and confirm.
Using relays the maintenance signal is transmitted via the 4-
20mA interface and the symbol [
] is displayed when the
alarm is set to off.
Configuring Relay A1 or A2
This function defines whether the alarm relay is energized
during normal operation or energized at an alarm condition.
If the configuration of the relay is set to “Normally energized”,
the relay contact is asserted during normal operation and
changes if an alarm is triggered. At a loss of power this will
trigger an alarm (fail-safe). The fault relay is factory-configured
to “Normally energized” and cannot be changed.
To configure relay A1 or A2:
1. Select
Settings > Instrument > Alarm > Relay A1
or
Relay A2
and confirm.
2. Select
Normally energ.
or
Energ. on alarm
and confirm.
Configuring Alarm A1 or A2
To configure alarm A1 or A2:
1. Select
Settings > Instrument > Alarm > Alarm A1
or
Alarm A2
and confirm.
The current alarm set-point is displayed.
2. Set the alarm set-point and confirm.
3. Select
Next
and confirm.
The current alarm direction is displayed.
4. Select
Rising
or
Falling
and confirm.
5. Select
Next
and confirm.
The current alarm latch mode is displayed.
6. Select
Latching
or
Non Latching
and confirm.
7. Select
Next
and confirm.
The current acknowledgement mode is displayed.
8. Select
Acknowledgeable
or
NonAcknowledgeabl
or
PreAcknowledgeabl
and confirm.
9. Select
Next
and confirm.
The current hysteresis is displayed.
10. Set the hysteresis and confirm.
11. Select
Next
and confirm.
A confirmation screen shows all settings.
12. Select
Confirm
and confirm with [OK].
The new settings are now saved.
Repeat settings for A1 or A2 respectively.
Case: Alarm is acknowledged before and after the alarm condition cleared.
Latching
Non-acknowledgeable
1
Alarm condition is present.
Relay (b) is energized and symbol (b) is active.
LED (c) starts flashing.
2
Alarm is about to be acknowledged (d), but acknowledging is not
possible.
Relay (b) stays energized and symbol (b) stays active.
LED (c) keeps flashing.
3
Alarm condition clears.
Relay (b) stays energized and symbol (b) stays active.
LED (c) keeps flashing.
4
Alarm is acknowledged (d).
Relay (b) and symbol (b) are reset.
LED (c) is off.
1
2 3
a
b
c
d
4
CAUTION
If the alarm is set to Off, an alarm condition will not be
shown by the LEDs, asserted relays or the fieldbus
output!
!
NOTICE
The hysteresis function defines an interval where a
triggered relay maintains its status until the gas
concentration is outside the defined interval. This
prevents relays from chattering at an alarm set-point.
Example: A2 at 40 % LEL Methane
Hysteresis: 3 % LEL
Alarm asserts at
≥
40 % LEL
Alarm de-asserts at
< 37 % LEL(= 40 % LEL - 3 % LEL)
i
i
Содержание Polytron 8100
Страница 2: ......
Страница 3: ...1 5 4 3 2 5 1 4 3 10 7 8 9 2 6 3 4 5 2 1 3 9 5 2 1 14 13 3 4 5 6 7 8 14 2 11 12 15 A B C D E...
Страница 4: ...1 2 3 4 1 2 1 2 3 4 1 2 VDC mA VDC mA F G I H J K L t s 1 1 mA 0 7 5 3 t s T 1 4 20 mA T 2 3 SAMPLE...
Страница 172: ...172 Dr ger Polytron 8100 1 1 1 Dr ger Dr ger Dr ger 6 196 Dr ger EN IEC 60079 1 II 1 5 5 1 5 6 1 5 7 2014 34 EC 1 2 i i...
Страница 174: ...174 Dr ger Polytron 8100 3 3 1 10 1 204 Hawke A501 421 A NPT NPT 10 9 210 20 7 12 4 8 55 C 25 C 5 7 3 174...
Страница 182: ...182 Dr ger Polytron 8100 4 5 1 4 3 OK OK OK OK 5 8 2 188 _ _ _ 1 _ _ _ 2 4 5 2 4 5 3 OK OK 4 5 4 OK 5 OK 3 3 2 2...
Страница 198: ...198 Dr ger Polytron 8100 6 2 3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 OK 6 6 1 1 196 6 1 2 196 Dr ger H2S ppm 25 i i 15 i i...
Страница 201: ...Dr ger Polytron 8100 201 6 4 B 1 2 2 2 3 3 4 5 4 Dr ger 5 6 7 2 22 8 9 6 2 196 10 SIL 5 6 185 5 10 4 193 i i i i...
Страница 223: ...Dr ger Polytron 8100 223 4 5 2 4 5 3 OK OK 4 5 4 OK 5 OK 3 3 2 2...
Страница 239: ...Dr ger Polytron 8100 239 6 4 B 1 2 2 2 mm 3 3 4 5 4 Dr ger 5 6 7 2 22 8 9 235 6 2 10 SIL 225 5 6 233 5 10 4 i i i i...
Страница 250: ...250 Polytron 8100 Additional Approvals A 3 Control Drawings...
Страница 252: ...252 Polytron 8100 Additional Approvals A 4 Declaration of conformity...
Страница 253: ......