8
Dräger Polytron 5200 / Dräger Polytron 53X0
Operation
3.2
Electrical installation without e-box
3.2.1
Power and signal wiring
z
Loosen set-screw and unscrew lid from instrument.
1. Pull out the bezel, by grasping the notches on either side of
the display with your fingers and pull it up.
z
Turn bezel over and pull off the 3-pin connector.
Connect the three wires for power and signal to the appropriate
terminal as indicated in the following wiring table and figure.
Fasten terminal screws with the correct torque according to the
table Tightening torque and wire size for field wiring terminal
see Section 8.6 on Page 24.
z
If operated as a stand-alone instrument, wire pin 1 to pin 3.
z
Plug connector back into socket.
z
The cable shielding should only be connected at the con-
troller.
z
Place bezel back into the enclosure.
z
Screw the lid back on, until it is seated (correct torque) see
Section 8.5 on Page 24, and tighten set-screw.
3.2.2
Relay option
If the relay option has been installed, the wires for the alarm
devices will be connected to the 9-pin connector.
z
Turn bezel over and pull off the 9-pin connector.
z
Connect the wires for alarm 1, alarm 2 and fault to the ter-
minals, as indicated in the following wiring table.
z
With factory default settings and during normal operation,
the relays are energized. This provides “fail-safe” opera-
tion. The terminal designators indicated in the following
wiring table are shown as factory default and normal oper-
ation mode, see Section 5 on Page 22.
z
Plug connector back into socket.
1 Connector for DrägerSensor DD, LC, and DSIR
3.2.3
Remote sensor
The remote junction box (part number 4544098 for stainless
steel or 4544099 for aluminum) allows sensor installation at a
location away from the instrument electronics. This remote in-
stallation permits easy setup when the sensor must be located
in a difficult to reach or awkward position, see Polytron 5000
Junction Box Instructions for Use 4544286 for more details.
CAUTION
Ensure wiring for relays and connections for sensor
are made before applying power.
3 Pin Connector (Power and Signal)
Pin
1
2
3
Mark
+
none
S
Function
V +
V -
4-20 mA
signal
!!
NOTICE
To ensure that a fault is recognized - without having to
look at the instrument - an alarm device must be con-
nected to the fault relay.
9 Pin Connector (Relays)
Fault Relay
A2 Relay
A1 Relay
Pin
1
2
3
4
5
6
7
8
9
Mark NO
C
NC
NO
C
NC
NO
C
NC
i
i
www.norrscope.com