53
3-11
Energy Saving Mode
s n Energy Saving Mode
3-11-1
Energy Saving Mode
OFF
ON
s s Energy Saving Mode
3-11-2
direct off
OFF
ON
s s Energy Saving Mode without NFD functionality is
executed
3-11-3
Power down speed %
1
30
99
s s Calculated power down speed if NFD is running in
energy saving mode in %
3-11-4
time direct off
0
5
9999
s s Time after the Energy Saving Mode without NFD
functionality is executed
3-12
FC failure behavior
e s FC failure behavior
3-12-1
behavior
OFF
Fixed Speed
s s behavior
3-12-2
Fixed Speed
s n Fixed Speed
3-12-2-1.1
Max power
100%
200%
300
%
400%
500%
600%
s s Limitation of the maximum power / maximum sys-
tem load (1 pump is 100%)
3-12-2-1.2
Max power (dummy)
0
300
600
n e used for mapping of selection ENUM value to
UIN16
3-12-2-2
Set point
0
400
1000
s c System pressure set point
3-12-2-3
Bandwidth
0
30
999
s c System pressure within doubled bandwidth
3-12-2-4
Min. run time
0
30
999
s c The minimum time of the pump to run. (the run
time correction will not drop below this value)
3-12-2-5
Max. run time
0
86400
356400
s s Maximum continuous run time of the pump. After
this time the pump will be forced to change over.
3-12-2-6
Start delay
0
2
999
s s Start delay to switch the pumps on when pressure
remains low
3-13
Pump Changeover
e s Pump change due to maximum run time
3-13-1
Supply reaction
Under pressure
Over pressure
e s Selection Under-/Oversupply
3-13-2
Changeover delay
0
10
e s Time delay between the changeover
3-14
By Pass Valve
e s By pass valve connected on the discharge side
3-14-1
Valve Function
Off
Check run
PT 1000
Digital Input
e s Function of the valve
Parameter
Disp
lay
text
Va
lu
e
1
descrip
tio
n
Min./Max
.
Read
Wr
it
e
Help
text