17
9
Hydro-unit configuration
9.1
Hydro-Unit MC
ATTENTION
See factory settings 3-2-2-1
When as a result of an increasing water volume the
pressure drops below the pressure set point, a pump
will be switched on. When the required system
pressure has been reached, the pumps are switched
off one at a time. The minimum run time related
switch-off delay is optimized constantly, which results
in a considerable energy saving.
Table 16: Specific parameter settings MC
Figure 3: 1 pump operation
Figure 4: 2 pump operation
Figure 5: 3 pump operation
Q
H
S
Q
H
S
Q
H
S
Parameter
Value
3-3-1
Number of pumps
1
2
3
4
5
6
3-3-2
Inlet
Switch
Pressure
Level / valve ON-OFF
Level / valve prop.
3-3-3
Discharge
Fixed Speed
3-5-1
Set point
... kPa
3-5-3
Bandwidth
30
3-5-13
Low pressure alarm
100
3-6-1
Opt. pump starts/h
10
3-6-2
Min. run time
Default 180 s
DOL
≤
2.2 kW 90 s
3-6-3
Min. run time corr.
10 s
3-6-8
Run-dry delay
Default 30 s
Float/level control 1 s