76
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-4-8-1
Trigger active high/low
Active low
1: Active low
Everybody
Service
-
2-4-8-2
Trigger delay
0 … 99 s
1 s
Everybody
Service
-
10.2.2.5 System protection
Table 33:
System protection parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-5
System protection
-
-
Everybody
Nobody
-
2-5-1
Dry running protection
-
-
Everybody
Nobody
-
2-5-1-1
Source
-
-
-
-
2-5-1-1-1
Source
No function
None
Everybody
Service
-
Pressure sensor on suction side
Pressure sensor at tank
Pressure switch
Float switch
Flow switch
2-5-1-1-2
Delay time for system stop
0 … 99 s
10 s
Everybody
Service
-
2-5-1-1-3
Delay time reset
0 … 99 s
2 s
Everybody
Service
-
2-5-1-1-4
Maximum number of dry running
protection events per hour
1 … 10
3
Everybody
Service
-
2-5-1-1-5
Dry running protection stop delay
1 … 5 s
1 s
Everybody
Service
-
2-5-1-2
Additional source
-
-
-
-
-
2-5-1-2-1
Additional source
No function
None
Everybody
Service
-
Pressure sensor on suction side
Pressure sensor at tank
Pressure switch
Float switch
Flow switch
2-5-1-2-2
Delay time for system stop
0 … 99 s
10 s
Everybody
Service
-
2-5-1-2-3
Delay time reset
0 … 99 s
2 s
Everybody
Service
-
2-5-1-3
Pressure sensor on suction side
-
-
Everybody
Nobody
-
2-5-1-3-1
Minimum suction-side pressure for
system stop
0 … maximum pressure sensor range
1 bar
Everybody
Service
-
Содержание Hydro-Unit Utility Line F
Страница 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Страница 58: ...58 96 ...
Страница 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Страница 93: ......
Страница 94: ......
Страница 95: ......